Plan Review Notes
Plan Review Notes For Permit 07110645
Permit Number 07110645
Review Stop E
Sequence Number 1
Notes
Date Text
2008-02-04 11:34:05 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} INDICATE IF THE ELECTRICAL SERVICE SHOWN ON SHEET 5
 IS NEW OR EXISTING. IF NEW INCLUDE IN THE DESCRIPTION
 ON THE APPLICATION, AND LOCATE ALL SERVICE EQUIPMENT ON
 THE PLAN, METER ENCLOSURE, DISCONNECTS AND PANELS, SO
 THAT COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE
 REVIEWED. PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND
 CONDUIT SIZE AND TYPE.
  
 2} GFI RECEPTACLES ARE REQUIRED IN THE KITCHEN PER
 210.8(B)(2).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.