Text |
| 2007-12-17 16:55:21 | 2004 FBC W/2007 REVISIONS |
| | LEVEL 2 ALTERATIONS AND ADDITION |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| | MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. NOTE: WORK MUST COMMENCE WITHIN |
| | 90 DAYS OF RECORDING DATE. |
| | |
| | 2)THE PROJECT IS LOCATED IN AN AREA WITH SOILS HAVING |
| | A QUESTIONABLE BEARING CAPACITY. SUBMIT A GEO-TECHNICAL |
| | EVALUATION SOIL REPORT. SEE FBC R401.4. |
| | |
| | 3) NO WHITE-OUT IS ALLOWED ON THE PLANS. SEE FBC |
| | 106.1.3* CITY AMENDMENTS. |
| | |
| | 4) THE CONSTRUCTION TYPE SPECIFIED ON SHEET A-1.0 IS |
| | INCORRECT. THE CONSTRUCTION TYPE IS V-B, TYPE VI IS NO |
| | LONGER IN THE CODE. SEE FBC 310. |
| | |
| | 5) THE WIND CRITERIA SPECIFIED AS FBC 2001, SECTION |
| | 1606ON A-1.0 IS INCORRECT. SEE FBC R301.2.1. |
| | |
| | 6) ON SHEET A-1.0, THE EDITION OF THE FBC IS |
| | INCORRECTLY SPECIFIED AS 2001. THE APPLICABLE CODE IS |
| | THE 2004 FBC. |
| | |
| | 7) SPECIFY THE TRUSS BOTTOM CORD LIVE LOAD ON THE |
| | PLANS. FBC TABLE R301.5 SPECIFIES THE LIVE LOAD FOR |
| | ATTICS WITH STORAGE AS 20 PSF. |
| | |
| | 8) SPECIFY WHAT METHOD OF TERMITE PROTECTION WILL BE |
| | USED. SEE FBC R320.1. |
| | |
| | 9) ON SHEET A-2.0 THE STRUCTURAL NOTES SPECIFY THE |
| | WRONG ACI EDITIONS. THE 2004 FBC REFERENCES ACI 315-02 |
| | AND ACI 530-05. |
| | |
| | 10) SHOW COMPLIANCE WITH FBC R310.1 FOR EMERGENCY |
| | ESCAPE AND RESCUE OPENINGS IN THE BEDROOM ADJACENT TO |
| | THE GARAGE ADDITION. |
| | |
| | 11) PROVIDE BUCK FASTENING DETAILS FOR THE SWING, |
| | SLIDING AND OVERHEAD GARAGE DOORS. SEE FBC R613.1.1. |
| | |
| | 12)SHOW COMPLIANCE WITH FBC R905.2.2 SLOPE. |
| | ASPHALT SHINGLES SHALL ONLY BE USED ON ROOF SLOPES OF |
| | TWO UNITS VERTICAL IN 12 UNITS HORIZONTAL (2:12) OR |
| | GREATER. FOR ROOF SLOPES FROM TWO UNITS VERTICAL IN 12 |
| | UNITS HORIZONTAL (2:12) UP TO FOUR UNITS VERTICAL IN 12 |
| | UNITS HORIZONTAL (4:12), TWO LAYERS OF UNDERLAYMENT |
| | COMPLYING WITH ASTM D 226 TYPE I OR TYPE II, ASTM D |
| | 4869 TYPE I OR TYPE II OR ASTM D 6757 IS REQUIRED IN |
| | ACCORDANCE WITH SECTION R905.2.7 . |
| | |
| | 13) PLEASE CLARIFY SECTION 1 ON A-4.0 WHICH SPECIFIES |
| | ANCHORING EACH TRUSS BOTTOM CORD WITH SIMPSON LTT19 |
| | ANCHORS. THEY APPEAR TO BE ANCHORED TO HOLLOW BLOCK. |
| | ALSO, CLARIFY WHAT IS OPTI-MESH 6" LONG? FBC 106.1.1* |
| | CITY AMENDMENTS. |
| | |
| | 14) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 15) THE PRODUCT APPROVAL DRAWING, FL-618, SUBMITTED FOR |
| | THE THERMA-TRU DOORS IS FOR THE FRAME ATTACHMENT AND |
| | REQUIRES A SEPARATE PRODUCT APPROVAL FOR THE DOOR |
| | PRODUCT. SEE GENERAL NOTES 2, 3 AND 6 ON SHEET 1 OF 3. |
| | |
| | 16) SPECIFY THE MOUNT TYPE AND FASTENING OPTION THAT |
| | WILL BE USED TO INSTALL THE STORM PANELS ON THE FRONT |
| | DOOR W/SIDELITES. CIRCLE THE APPROPRIATE ITEMS ON THE |
| | NOA. |
| | |
| | - ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |