| Plan Review Notes For Permit 07110619 |
| Permit Number |
07110619 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2008-03-04 10:25:42 | REVISION CHECKLIST: | | | | | | 1- PROVIDE PRODUCT APPROVAL FOR GARAGE DOORS THAT MEET | | | THE DESIGN PRESSURES CALCULATED BY THE ARCHITECT. | | | | | | ***REMAINDER: ARCHITECT TO REVIEW AND APPROVE PRODUCT | | | APRPOVAL IN WRITING PRIOR TO SUBMITTAL TO THIS OFFICE. | | | SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. | | | | | | 2- CLEARLY MARKON ALLWINDOW/DOOR MULLIONPRODUCT | | | APPROVALS THE SPECIFIC MULLION SIZEAND ANCHORING TO | | | VERIFY COMPLIANCE WITH SEC. R301 AND THE CALCULATED | | | DESIGN PRESSURES. | | | | | | (NOTE: THERE ARE MANY SIZES THAT DON'T RESIST THE | | | DESIGN PRESSURES, THAT'S WHY THIS IS REQUESTED PRIOR TO | | | INSTALLATION TO AVOID CONFLICTS OR DELAYS. THIS | | | COMMENT APPLIES TO DOORS AND WINDOWS ALSO). | | | | | | 3- CLEARLY MARK ON ALL WINDOWS AND DOORSPRODUCT | | | APPROVALSTHE SPECIFIC WINDOW AND DOORS TO BE | | | INSTALLED TO VERIFY COMPLIANCE WITH SEC. R301 AND THE | | | CALCULATED DESIGN PRESSURES. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|