2008-01-24 10:04:54BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- PROVIDE 2 COPIES OF SOIL TEST REPORT.THEY WERE
 NOTSUBMITTED WITH RE-SUBMITTAL PACKAGE.SEC. R401.4
 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 2- REVISED ENERGY CALCULATIONS ARE TAKING THE CEILING
 FAN CREDIT.NEED TO PROVIDE REVISED ELECTRICALPLAN
 SHOWINGCEILING FAN SIZE IN ALL ROOMSTO VERIFY
 COMPLIANCE WITHTABLE 13-607.1.A.1 FBC 2004.
  
 3- REVISE DOOR BUCK DETAIL.1 1/2" LONG TAPCON IS NOT
 LONG ENOUGH TO BE USED ON A 2X BUCK. REVISE AS
 REQUIRED.
  
 NOTE: ADDED 2-11-08:REVISE BUILDING EXPOSUREFROM
 "B" TO "C" AND THE DESIGN PRESSURES AS REQUIRED BY SEC.
 R301.2.1.4(3).