| Plan Review Notes For Permit 07110619 |
| Permit Number |
07110619 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-01-24 10:04:54 | BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | 1- PROVIDE 2 COPIES OF SOIL TEST REPORT.THEY WERE | | | NOTSUBMITTED WITH RE-SUBMITTAL PACKAGE.SEC. R401.4 | | | OF 2004 FLORIDA RESIDENTIAL CODE. | | | | | | 2- REVISED ENERGY CALCULATIONS ARE TAKING THE CEILING | | | FAN CREDIT.NEED TO PROVIDE REVISED ELECTRICALPLAN | | | SHOWINGCEILING FAN SIZE IN ALL ROOMSTO VERIFY | | | COMPLIANCE WITHTABLE 13-607.1.A.1 FBC 2004. | | | | | | 3- REVISE DOOR BUCK DETAIL.1 1/2" LONG TAPCON IS NOT | | | LONG ENOUGH TO BE USED ON A 2X BUCK. REVISE AS | | | REQUIRED. | | | | | | NOTE: ADDED 2-11-08:REVISE BUILDING EXPOSUREFROM | | | "B" TO "C" AND THE DESIGN PRESSURES AS REQUIRED BY SEC. | | | R301.2.1.4(3). |
|