| 2007-12-03 09:07:52 | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} THE ARCHITECTURAL FIRM WHOSE TITLE BLOCK APPEARS ON | | | THE PLANS, MUST SIGN AND SEAL THE PLAN PER | | | 481.221(1)(B)FS. | | | | | | 2} R313.1 SMOKE ALARMS. | | | SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING | | | LOCATIONS: | | | 1. IN EACH SLEEPING ROOM. | | | 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE | | | VICINITY OF THE BEDROOMS. THE SINGLE ALARMLOCATED IN | | | THE HALL SERVING 3 BEDROOMS DOES NOT MEET THE INTENT OF | | | THIS CODE. | | | | | | 3} 210.52 (H), HALLWAYS IN DWELLING UNITS, HALLWAYS OF | | | 3.0 M (10 FT) OR MORE IN LENGTH SHALL HAVE AT LEAST ONE | | | RECEPTACLE OUTLET.ADD PER THIS ARTICLE. | | | | | | 4} CIRCUITS 19 AND 21 IN PANEL "B" MUST BE 20 AMP TO | | | COMPLY WITH 210.11(C)(3). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | 2007-12-03 07:55:35 | | | | | | | |
|