2007-12-14 16:57:48NEW SFR BUILDING REVIEW FIRST CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- PROVIDERECORDED NOTICE OF COMMENCEMENT.SEC.
 713.13 FLORIDA STATUTE.
  
 2- PAY IMPACT FEES. BRING BACK STAMPED PLANS AND COPY
 OF PAID RECEIPT.
  
 3- SURVEYS TO HAVE ORIGINAL SIGNATURE AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTE.
  
 4- AREA CALCULATION NEED TO INCLUDE REAR PORCH AREA BY
 THE BREAKFAST AND LIVING ROOM AREA TO PROPERLY ASSESS
 THE PERMIT VALUATION AND RADON FEES.FEES WILL BE
 ADJUSTED ONCE TOTAL AREA IS INCLUDED.
  
 5- SPECIFY DOOR LEADING TO THE LIVING AREA FROM THE
 GARAGE AREA TO SHOW COMPLIANCE WITH SEC. R309.1 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 6- PROVIDE COMPLETE SPECIFICATIONS FOR BBQ HOOD LISTED
 AND APPROVED FOR EXTERIOR INSTALLATION AS SHOWN ON
 PLANS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
 INFORMATION SUBMITTED DOESN'T SPECIFY THAT HOOD WAS
 DESIGNED AND APPROVED FOR EXTERIOR INSTALLATION.
  
 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) PRECAST LINTELS. NOA 03-0605.04 SUBMITTED IS FOR
 4", 6" AND 12" LINTELS, NOT FOR 8" LINTELS AS SPECIFIED
 ON PLANS.
  
 B) WINDOW MULLIONS. NONE SUBMITTED AT THIS TIME.
  
 C) ALL SIMPSON, SEMCO OR USP STRUCTURAL CONNECTORS
 SPECIFIED ON PLANS.
 ***NOTE:PROVIDETHE FLORIDA PRODUCT APPROVALCOVER
 PAGE AND PAGE SHOWING THE CONNECTOR ONLY. NO NEED TO
 SUBMIT THE FULL REPORT. SOME OF THE PRODUCT APPROVALS
 ONLY PROVIDED THE COVER PAGE AND THEY ARE MISSING THE
 PAGE WITH THE SPECIFIC CONNECTOR.
  
 D) 9'-0" WIDE GARAGE DOORS AS SHOWN ON PLANS.
 PRODUCT APPROVAL SUBMITTED ARE FOR 16' WIDE DOORS.
  
 E) FIXED WINDOW 6060 IN MASTER BEDROOM. PRODUCT
 APPROVAL SUBMITTED DOESN'T COVER THIS WINDOW SIZE.
  
 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
  
 9- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 106.1.1.2CITY AMENDMENTSTO FBC
 2004 TO VERIFY COMPLIANCE WITH UPLIFT RESISTANCE SHOWN
 ON THE PRODUCT APPROVAL.DON'T SPECIFY PER PRODUCT
 APPROVAL.IF USING NAILS OR SCREWS, THEN SPECIFY TYPE
 AND NUMBER. IF USING POLYFOAM, THEN PROVIDE PRODUCT
 APPROVAL. SEE NOA SUBMITTED FOR TYPE OF POLYFOAM TO BE
 USED.
  
 10- PROVIDE ROOF SHEATHING SPECIFICATIONS. SEE SEC.
 R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE FOR MIN.
 TYPE,SIZE AND SPACING OF NAIL TO BE USED, INCLUDING
 ROOF ZONES #3.
  
 11- PROVIDE AT LEAST ONE BATHROOM WITH DOORHAVING 29"
 MIN. CLEAR OPENING AS REQUIRED BY SEC. 11-11.1 FBC
 2004.
  
 12- SOME EXTERIOR ELEVATIONS ARE MISSING THE OPENING
 DESIGN PRESSURES. PROVIDE ALL THE DESIGN PRESSURES FOR
 ALL OPENINGS, INCLUDING THE GARAGE DOORS AS REQUIRED BY
 SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 13- ONLY THE COVER PAGE WAS SIGNED AND SEALED. ALL
 DRAWINGS NEED TO BE SIGNED, SEALED AND DATED AS
 REQUIRED BY CHAPTER 481 FLORIDA STATUTE.
  
 14- ENERGY CALCULATIONS:
 A) REVISE CEILING ATTIC AREA. SEE SEC. 13-604.1.A.1
 FBC 2004 AND REVISE AS REQUIRED.
  
 B) REVISE OVERHANG LENGTH AND HEIGHT. SEE DRAWINGS
 FOR CORRECT INFORMATION AND REVISE AS REQUIRED.
  
 15- SHEET A1:
 A) UPDATE CODE REFERENCE REVISIONS. CURRENT
 REVISIONS ARE 2007, NOT 2006.
  
 B) CLARIFY/REVISE WHY MIN. SOIL BEARING PRESSURE IS
 N/A?.
  
 16- SHEET A3:
 A) CLARIFY/REVISEFOOTING SHOWN ON FOUNDATION PLAN
 BYONE CAR GARAGE.
  
 B) PROVIDE COMPLETE DESIGN PLANS, DETAILS AND
 SPECIFICATIONS FOR SCREEN ENCLOSURE TO VERIFY
 COMPLIANCE WITH CHAPTER 20 FBC 2004.. OTHERWISE,
 PROVIDE COMPLETE INFORMATION UNDER A SEPARATE PERMIT.
  
 17- SHEET A5:
 A) UPDATE TRUSS ANCHOR SCHEDULE. SEE CURRENT CATALOG
 FOR NUMBER/SIZE OF NAILS AND ALL LOADS FOR WHICH
 CONNECTORS ARE DESIGNED AND REVISE AS REQUIRED.
 OTHERWISE, PROVIDE COMPLETE ENGINEERING ANALYSISWHEN
 NAILS AND LOADS DON'T MATCH THOSE TESTED AND PUBLISHED
 BY THE MANUFACTURER. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 B) CLARIFY TYPE OF CONNECTOR SPECIFIED ON ROOF
 FRAMING PLAN BY FAMILY ROOM, LANAI AND BEDROOM #5 AREA.
 THERE ARE TWO DIFFERENT CONNECTORS SHOWN. SEE COMMENTS
 ON PLANS AND REVISE AS REQUIRED.
  
 C) SPECIFY CONNECTORS FOR TRUSS GIRDER IN REAR PORCH
 BY THE BREAKFAST AREA. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 D) NEED TO SPECIFY WOOD TO MASONRY CONNECTOR FOR
 TRUSS GIRDER ABOVE MASTER BEDROOM AREA.THD28-2 IS A
 WOOD TO WOOD CONNECTOR. REVISE AS REQUIRED. SEE CATALOG
 FOR PROPER CONNECTOR.
  
 E) ROOF FRAMING PLAN ABOVE ENTRY PORCH IS INCORRECT.
 COLUMNS ARE SHOWN OUTSIDE OF ROOF AREA. REVISE AS
 REQUIRED.
  
 18- SHEET A7:
 A) REVISE STRUCTURAL BUCK DETAILS FOR DOORS AND
 WINDOWS.NEED TO PROVIDE FULL SUPPORT TO THE FRAMING.
 SEE SEC. R613.6.1.1 OF 2004 FLORIDA RESIDENTIAL CODE
 AND REVISE DETAIL AS REQUIRED.
  
 B) REVISE CONNECTOR SPECIFIED ON TYP. WALL SECTION.
 "HUGHES"IS OUT OF BUSINESS. REVISE AS REQUIRED. ALSO,
 REVISE "SEMCO" CONNECTOR SPECIFIED ON SECTION SHOWN ON
 SAME DRAWING ON THE BOTTOM LEFT HAND SIDE.COORDINATE
 WITH TRUSS ANCHOR SCHEDULE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER