| Plan Review Notes For Permit 07110597 |
| Permit Number |
07110597 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2008-02-05 17:50:26 | REVISED SHEETS S-1, E-1 AND E-2 | | | SHEET S-1 WAS FOR REVISION OF ELEC ONLY, STILL NEED TO | | | USE ORIGINAL PLANS FOR ANY STAMPS OR REVIEWED ITEMS | | | FROM OTHER TRADES. | | | | | | REDLINED SHEET E-1 AS THE RISER HAS BEEN REVISED FOR | | | NEW CONDUCTORS FROM MAIN TO FPL TRANSFORMER AND NOW | | | SHOWS NEW *EQUIPMENT GROUNDING CONDUCTORS* FROM FPL TO | | | FIRST MEANS OF DISCONNECT WHICH IS NOT PERMITTED. | | | PLEASE SEE 250.6 AND 250.24 . IF THESE ARE INSTALLED | | | THIS WOULD CREATE OBJECTIONABLE CURRENTS WHICH IS NOT | | | PERMITTED BUT ALSO A SAFETY ISSUE WITH SERVICE. PLEASE | | | REMOVE. |
|