| Date |
Text |
| 2007-12-21 09:52:30 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. OK |
| | |
| | 2. SHT S-1 INDICATES SHT 1 OF 2, BUT NO SHT 2 |
| | SUBMITTED. PLEAE CLARIFY. SECTION 106.1.1. |
| | ****NO RESPONSE, NOT ADDRESSED. ALSO ALL THREE SHEETS |
| | ARE INDICATED AS SHEET E-2 OF 2 IN THE TITLE BLOCK. |
| | PLEASE CLARIFY. |
| | |
| | 3. OK |
| | 4. OK |
| | |
| | 5. SHT S-1 INDICATE THE MEASUREMENT OFF ALL STRUCTURES |
| | TO THE SIDES OF THE GENERATOR. (WALLS & BUILDING). |
| | SECTION 106.1.2. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 6. SUBMIT THE INSTALLATION INSTRUCTIONS FOR THE |
| | GENERATOR SHOWING REQUIRED CLEARANCE ON ALL SIDES OF |
| | THE GENERATOR FOR SERVICE ETC. SECTION 106.1.2. |
| | ****RESPONSE WAS THE SUBMITTAL OF A SINGLE SHEET THAT |
| | DOES NOT INDICATE WHAT BRAND OR MODEL GENERATOR THE |
| | SHEET IS FOR. ALSO 3' IS HAND WRITTEN ON THE SHEET, BUT |
| | NOT FROM THE MANUFACTURE. PLEASE SUBMIT THE COMPLETE |
| | INSTRALLTAION INSTRUCTIONS FOR THE GENERATOR BEING |
| | INSTALLED. CLEARANCES FROM ALL STRUCTURES SHALL BE |
| | INDICATED. |
| | |
| | 7. THE GENERATOR SHALL BE LISTED. PLEASE SUBMIT |
| | INFORMATION SHOWING REQUIRED LISTING. SECTION 301.3 |
| | FUEL GAS CODE. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 8. OK DEDICATED METER |
| | 9. OK |
| | 10. OK |
| | 11. OK |
| | 12. OK |
| | |
| | **********NEW COMMENT********** |
| | |
| | 1B. SEE ATTACHED SHEET CONCERNING THE DESIGN |
| | PROFESSIONAL AND FS 553.80(2)(B). THIS IS GIVEN AS A |
| | NOTICE ONLY AT THIS TIME. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |