| Date |
Text |
| 2007-12-11 09:23:29 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. INDICATE THE CODE IN EFFECT AT THE TIME OF DESIGN. |
| | (FBC-2004 W/2007 AMENDMENTS) |
| | |
| | 2. SHT S-1 INDICATES SHT 1 OF 2, BUT NO SHT 2 |
| | SUBMITTED. PLEAE CLARIFY. SECTION 106.1.1. |
| | |
| | 3. SHTS S-1, E-1 & E-2 THE ENGINEER SHALL LEGIBLY |
| | INDICATE THEIR NAME AND LICENSE NUMBER ON EACH SHEET. |
| | FAC 61G15-23.002(2) & FS 471.025. |
| | |
| | 4. SHT E-2 SHALL BE SIGNED, SEALED, DATED AS REQUIRED |
| | BY FLORIDA STATUTES & SECTION 106.1. |
| | |
| | 5. SHT S-1 INDICATE THE MEASUREMENT OFF ALL STRUCTURES |
| | TO THE SIDES OF THE GENERATOR. (WALLS & BUILDING). |
| | SECTION 106.1.2. |
| | |
| | 6. SUBMIT THE INSTALLATION INSTRUCTIONS FOR THE |
| | GENERATOR SHOWING REQUIRED CLEARANCE ON ALL SIDES OF |
| | THE GENERATOR FOR SERVICE ETC. SECTION 106.1.2. |
| | |
| | 7. THE GENERATOR SHALL BE LISTED. PLEASE SUBMIT |
| | INFORMATION SHOWING REQUIRED LISTING. SECTION 301.3 |
| | FUEL GAS CODE. |
| | |
| | 8. PLEASE INDICATE IF THE GAS METER IS A DEDICATED |
| | METER FOR THE GENERATOR ONLY. IF NOT PLEASE INDICATE |
| | THE TOTAL BTU LOAD ON THE SYSTEM, AND SHOW THE TOTAL |
| | DEVELOPED LENGTH FOR ALL OTHER GAS LINES OFF THE METER. |
| | INDICATE WHERE THE OTHER GAS LINE CONNECTS AT THE |
| | METER. |
| | |
| | 9. GAS ISOMETRIC SHEET SHOWS A CLOCK VALVE. PLEASE |
| | INDICATE WHAT A CLOCK VALVE IS AND SUBMIT MANUF. |
| | SPECIFICATION FOR THE CLOCK VALVE. |
| | |
| | 10. GAS ISOMETRIC SHEET A SHUT OFF VALVE AND UNION ARE |
| | REQUIRED IMMEDIATELY UPSTREAM OF THE REGULATOR. SECTION |
| | 409.4. |
| | |
| | 11. THE PRINTED NAME AND SIGNATURE OF THE PERSON |
| | DESIGNING THE GAS PIPING SHALL BE ON THE GAS ISOMETRIC |
| | RISER DIAGRAM. SECTION 106.1.3. |
| | |
| | 12. SUBMIT THE MANUF SPECIFICATION SHEETS FOR THE GAS |
| | REGULATOR. INDICATE THE MODEL NUMBER USED. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |