| Date |
Text |
| 2007-12-10 12:22:15 | **** DENIED **** |
| | |
| | 1) NOTE: PLEASE SEE THE FOLLOWING CODES SHALL BE STATED |
| | ON PLANS. MAY NOT STATE *LATEST CODE*. |
| | PLEASE LIST THE FOLLOWING AS ADOPTED BY THE FLORIDA |
| | STATUTES. |
| | 2004 FBC W/2007 REVISIONS. |
| | 2002 NFPA-110 |
| | 2003 NFPA-101 |
| | 2005 NFPA-70 |
| | |
| | 2) NOTE: PLEASE KNOW BASED ON RECENT INFORMATION FROM |
| | THE STATE THE LICENSE WHICH MUST BE USED TO APPLY FOR |
| | INSTALL AND DEAL NATURAL GAS OR LP. |
| | PLEASE PROVIDE LICENSING FOR INSTALL/SALES OF UNIT. |
| | PLEASE SEE FS 527.02 |
| | |
| | 3) NOTE: PLEASE SEE PLANS INDICATE THE GENERATOR AS |
| | EXISTING IN TWO DIFFERENT LOCATIONS. PLEASE CLEARLY |
| | INDICATE WHERE THE NEW GENERATOR IS BEING INSTALLED. |
| | PLEASE SEE NFPA-110CHAPTER 7 FOR LOCATION |
| | INSTALLATIONS. |
| | |
| | 4) NOTE: PLEASE CLARIFY THE LOADS OF THE GENERATOR. |
| | PLEASE SEE RISER NOTES THERE WILL BE A MANUAL TRANSFER |
| | SWITCH HOWEVER PLANS ALSO NOTE THERE WILL BE A AN |
| | AUTOMATED TRANSFER SWITCH. WHICH ONE IS BEING |
| | INSTALLED? |
| | PLEASE KNOW IF THERE ARE ANY LIFE SAFETY OR LEGALLY |
| | REQUIRED LOADS BEING FED FROM THIS SOURCE AS THE |
| | PRIMARY BACK UP, THEN ON-SITE FUEL IS REQUIRED PER |
| | 701.11B3 AND 700.12B3. |
| | PLEASE KNOW IF THERE IS ANY LIFE SAFETY AND LEGALLY |
| | REQUIRED LOADS SERVED PLEASE SEE 700.6, 701.7 FOR |
| | TRANSFER EQUIPMENT |
| | |
| | 5) NOTE: PLEASE SEE THE RISER IS NOW SHOWING A NEW MAIN |
| | DISCONNECT BEING INSTALLED ON WHAT APPEARS TO BE THE |
| | LINE SIDE OF THE PREVIOUS MAIN SERVICE SWITCHGEAR. |
| | PLEASE SEE NEC 110.9 AND SUBMIT AIC RATINGS FOR ANY NEW |
| | SERVICE EQUIPMENT. |
| | FBC 106.3.5.1.2, 106.1.2 |
| | |
| | 6) NOTE: PLEASE SEENOT ALL SHEETS ARE SIGNED, DATED |
| | AND SEALED BY THE DESIGNER OF RECORD AS REQUIRED PER FS |
| | 471.003, 471.025 |
| | |
| | 7) NOTE: PLEASE COMPLETE INFORMATION ON TITLE BLOCKS |
| | FOR ALL SHEETS AS REQUIRED PER FAC 61G15-23.002 |
| | PLEASE SEE MISSING PRINTED NAME AND PRINTED LICENSE |
| | NUMBER OF THE ENGINEER OF RECORD. |
| | |
| | 8) NOTE: PLEASE SEE THE SIZING OF CONDUCTORS MAY ONLY |
| | USE THE 75 DEGREE COLUMN AS 110.14 ONLY CONTAINS A |
| | RATING FOR LUGS. |
| | PLEASE KNOW DE-RATING MAY BE USE 90 DEGREE COLUMN. |
| | |
| | 9) NOTE: PLEASE INCLUDE CONDUCTORS FROM NEW MAIN TO |
| | FPL. |
| | 230, 310.16, 240.4 |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |