| Date |
Text |
| 2008-04-04 13:14:33 | GAS PLAN REVIEW: |
| | REVISION DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET P1 GAS RISER: THE CUT SECTIONS OF PIPE FROM |
| | THE METER TO THE SEDIMENT TRAP DO NOT HAVE |
| | CORRESPONDING LENGTHS INDICATED. THE DISTANCE FROM THE |
| | POINT OF DELIVERY TO THE MOST DISTANT OUTLET IN |
| | INCORRECTLY BEING INDICATED AS 100 FEET. THE CALCULATED |
| | DISTANCE OF THE INDICATED CUT SECTIONS CORRESPONDING |
| | LENGTHS IS NOW 105 FEET AND THATS WITHOUT THE CUT |
| | SECTIONS FROM THE METER TO THE SEDIMENT TRAP. PLEASE |
| | CORRECT PLANS WITH ALL CORRESPONDING LENGTHS TO ALL CUT |
| | SECTIONS OF PIPE AND THE CORRECT LONGEST LENGTH OF THE |
| | SYSYEM. PER FBC FUEL GAS 401.1 SCOPE. |
| | |
| | 2. SHEET P1 GAS RISER: THE GAS BRANCH SUPPLY TO THE |
| | FOLLOWING APPLIANCES ARE INCORRECTLY SIZED. PLEASE |
| | CORRECT PER FBC FUEL GAS TABLE 402.4 (2). PLEASE |
| | REFERENCE FBC FUEL GAS TABLE 402.4(2) ATTACHED TO THESE |
| | COMMENTS FOR THE NEXT REVISION SUBMITTAL. |
| | |
| | A} ITEM #18, SHOULD BE 1 INCH. |
| | |
| | B} ITEM #19, SHOULD BE 1-1/4 INCH. |
| | |
| | C} ITEM #27, SHOULD BE 1 INCH. |
| | |
| | D} ITEM #32, SHOULD BE 1 INCH. |
| | |
| | E} ITEM #29, SHOULD BE 1-1/4 INCH. |
| | |
| | F} ITEM #30, SHOULD BE 1-1/4 INCH. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |