Plan Review Notes
Plan Review Notes For Permit 07110587
Permit Number 07110587
Review Stop P
Sequence Number 2
Notes
Date Text
2008-02-22 18:13:50DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 A. ALL SHEETS. THE TITLE BLOCK OF THE ARCHITECT FIRM
 SHALL INCLUDE THE FIRM LICENSE NUMBER. FAC
 61G1-16.004(2) & FS 481.219, 481.2055.
 ****NO RESPONSE, BUT NOT SHOWN IN THE TITLE BLOCKS FOR
 THE M-E-P SHEETS.
  
 B. ROUTE THE PLANS TO THE DEPT. OF BUSINESS REGULATION,
 HOTEL & RESTAURANT DIVISION FOR REVIEW. EACH SET OF
 PLANS SHALL HAVE A STAMPED/REVIEWED SHEET SUBMITTED
 WITH THE TWO PAGE "SPECIFICATION WORKSHEETS" ATTACHED
 TO THE SHEET STAMPED BY DBPR PRIOR TO RESUBMITTING.
 SECTION 102.2.1.
 ****NO RESPONSE, THE SPECIFICATION WORKSHEETS HAVE NOT
 BEEN ATTACHED TO THE SHEET STAMPED BY DBPR.
  
 C. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED FOR THE PERMIT.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. FOR ALL EXISTING PIPE.
 ****RESPONSE NOTED, BUT THE LENGTH OF PIPE FROM THE
 MAIN GAS LINE TO THE DROP IS NOT INDICATED ON THE
 RISER. ALL PIPING DOWNSTREAM OF RANGE/OVEN (30) SHALL
 BE DELETED, OR THE DEVELOPED LENGTH WILL BE INDICATED
 TO THE MOST REMOTE APPLIANCE AND THE PIPE SIZE AND ALL
 LENGTHS OF SECTIONS AS WELL AS MAXIMUM BTU LOAD WILL BE
 INDICATED FOR THE TWO PLUGED APPLIANCES. MANY PIPE
 SIZES ARE INCORRECT FOR THE DROPS AND 2-1/2" IS
 REQUIRED UP TO THE DROP PICKING UP THE FRYERS (27).
 (THIS HAS BEEN SIZED USING A MAXIMUM 100 FEET TOTAL
 DEVELOPED LENGTH. IF THE TOTAL DEVELOPED LENGTH IS
 INDICATED AS MORE THEN THE PIPING WILL BE SIZED BY THE
 NEXT LINE UP IN THE TABLE WHICH IS 125 FEET.) TABLE
 402.4(2).--MORE INFORMATION IS REQUIRED. IS ALL THE
 GAS PIPING TO BE RUN BELOW THE CEILING? OR IS THERE NO
 CEILING IN THE PREP KITCHEN? PLEASE CLARIFY. SECTION
 106.1.2.
  
 2. OK
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****RESPONSE NOTED, INFORMATION TO BE VERIFIED ONCE
 COMMENT 1. INFORMATION RECIEVED
  
 4. OK
  
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT NO MANUF. SHEETS WERE
 SUBMITTED.
  
 6. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ****RESPONSE NOTED, BUT PLEASE VERIFY IF THERE IS A
 CEILING IN THE PREP KITCHEN.
  
 **********NEW COMMENT**********
  
 1B. SHT P1 NOTE STATES "SYSTEM SIZED BY FBC 2004 FUEL
 GAS CODE TABLE A.3.1(4)",WHICH IS IN CONFLICT WITH
 THE NOTE THAT STATES "GAS PIPING SIZED AS PER FBC-2004
 FUEL GAS TABLE 402.4(2)". PLEASE DELETE NOTE
 REFERENCING TABLE A.3.1.4(4) AS THERE IS NO TABLE
 A.3.1.4(4) IN THE FBC-2004 FUEL GAS CODE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]