| 2007-12-07 14:16:12 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 AMENDMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. PG M1: ON THE ?RELOCATED? SIDE OF THE PLAN, AHU 2 IS |
| | SHOWN AT BOTH THE EXISTING LOCATION AND THE NEW |
| | LOCATION. PLEASE SHOW THE AHU ONLY IN THE NEW LOCATION |
| | FOR CLARIFICATION OF THE SCOPE OF WORK. FBC 106.1.1 |
| | |
| | 2. PG M1: MECHANICAL NOTE #13 CALLS FOR CONDENSATE |
| | DISPOSAL IN THE ROOF DRAIN. HOW IS CONDENSATE FOR AN |
| | AHU ON THE 1ST FLOOR TO DRAIN ON THE ROOF? PLEASE SHOW |
| | MEANS OF CONDENSATE DISPOSAL IN ACCORDANCE WITH FBC, M |
| | 307.2.1. ALSO, SHOW MEANS OF AUXILIARY DRAIN PROTECTION |
| | PER FBC, M 307.2.3. |
| | |
| | 3. RELOCATION OF AHU 2 WILL ALSO REQUIRE THE RELOCATION |
| | OR NEW INSTALLATION OF A DUCT SMOKE DETECTOR IN |
| | ACCORDANCE WITH FBC, M 606.2.1. THIS DETECTOR SHALL BE |
| | CONNECTED TO THE BUILDING FIRE ALARM SYSTEM IN |
| | ACCORDANCE WITH FBC, M 606.4.1. SHOW COMPLIANCE WITH |
| | THESE SECTIONS. |
| | |
| | 4. PG M1: MANY OF THE NOTES WHICH INDICATE THE SCOPE OF |
| | WORK RELATED TO RELOCATION OF AHU 2 ARE CURRENTLY PART |
| | OF THE SCOPE OF WORK WITHIN A SEPARATE PERMIT |
| | APPLICATION WITH DIFFERENT CONTRACTORS AND DIFFERENT |
| | DESIGNERS. PERMIT #07080934 IS FOR THE PURPOSE OF |
| | ADDING A FIRE RATED TENANT SEPARATION WALL TO SPLIT THE |
| | RETAIL SPACE FROM THE RESTAURANT. PLEASE VERIFY THAT |
| | THE SCOPE OF WORK RELATED TO ONE PERMIT IS NOT IN |
| | CONFLICT OR BEING DUPLICATED ON THE OTHER. FBC 106.1.1 |
| | |
| | |