Plan Review Notes
Plan Review Notes For Permit 07110587
Permit Number 07110587
Review Stop M
Sequence Number 1
Notes
Date Text
2007-12-07 14:16:12REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 AMENDMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PG M1: ON THE ?RELOCATED? SIDE OF THE PLAN, AHU 2 IS
 SHOWN AT BOTH THE EXISTING LOCATION AND THE NEW
 LOCATION. PLEASE SHOW THE AHU ONLY IN THE NEW LOCATION
 FOR CLARIFICATION OF THE SCOPE OF WORK. FBC 106.1.1
  
 2. PG M1: MECHANICAL NOTE #13 CALLS FOR CONDENSATE
 DISPOSAL IN THE ROOF DRAIN. HOW IS CONDENSATE FOR AN
 AHU ON THE 1ST FLOOR TO DRAIN ON THE ROOF? PLEASE SHOW
 MEANS OF CONDENSATE DISPOSAL IN ACCORDANCE WITH FBC, M
 307.2.1. ALSO, SHOW MEANS OF AUXILIARY DRAIN PROTECTION
 PER FBC, M 307.2.3.
  
 3. RELOCATION OF AHU 2 WILL ALSO REQUIRE THE RELOCATION
 OR NEW INSTALLATION OF A DUCT SMOKE DETECTOR IN
 ACCORDANCE WITH FBC, M 606.2.1. THIS DETECTOR SHALL BE
 CONNECTED TO THE BUILDING FIRE ALARM SYSTEM IN
 ACCORDANCE WITH FBC, M 606.4.1. SHOW COMPLIANCE WITH
 THESE SECTIONS.
  
 4. PG M1: MANY OF THE NOTES WHICH INDICATE THE SCOPE OF
 WORK RELATED TO RELOCATION OF AHU 2 ARE CURRENTLY PART
 OF THE SCOPE OF WORK WITHIN A SEPARATE PERMIT
 APPLICATION WITH DIFFERENT CONTRACTORS AND DIFFERENT
 DESIGNERS. PERMIT #07080934 IS FOR THE PURPOSE OF
 ADDING A FIRE RATED TENANT SEPARATION WALL TO SPLIT THE
 RETAIL SPACE FROM THE RESTAURANT. PLEASE VERIFY THAT
 THE SCOPE OF WORK RELATED TO ONE PERMIT IS NOT IN
 CONFLICT OR BEING DUPLICATED ON THE OTHER. FBC 106.1.1
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]