Plan Review Notes
Plan Review Notes For Permit 07110587
Permit Number 07110587
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-12-24 15:48:49*****DENIED*****
  
 01.THE SUITE NUMBER SHALL BE INCLUDED WITH THE
 NUMERICAL ADDRESS LOCATED IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 02.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 04.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 05.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY OR
 THE VICINITY THEREOF (INCLUDING STREETS, ROADS, FIRE
 LANES).
  
 06.PROVIDE THE OCCUPANT LOAD , AS IN THE NUMBERS OF
 PERSONS FOR WHOM MEANS OF EGRESS AND OTHER PROVISIONS
 ARE REQUIRED.
  
 07.PLEASE SHOW TRAVEL DISTANCE TO EXITS ON THE LIFE
 SAFETY PLAN SHEET.
  
 08.ANY DOOR IN A REQUIRED MENS OF EGRESSFROM AN
 AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS
 SHALL BE PROVIDED WITH PANIC HARDWARE OR FIRE EXIT
 HARDWARE.
  
 09.SPECIFY THE INTERIOR FINISH MATERIALS FOR THE NEW
 WALLS IN TERRMS OF CLASS A, CLASS B, OR CLASS C.
  
 10.PLANS DON' T INDICATE IF THE PROJECT SITE IS FIRE
 SPRINKLERED.IF SO SPRINKLERED AND THERE IS A CAUSE
 FOR THIS SYSTEM TO BE ALTERED DUE TO THE SCOPE OF WORK,
 SEPARATE PLANS AND PERMIT WILL BE REQUIRED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  