| Date |
Text |
| 2007-12-24 15:48:49 | *****DENIED***** |
| | |
| | 01.THE SUITE NUMBER SHALL BE INCLUDED WITH THE |
| | NUMERICAL ADDRESS LOCATED IN THE TITLE BLOCK OF EACH |
| | SUBMITTED PLAN SHEET. |
| | |
| | 02.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE |
| | REFERENCED. |
| | |
| | 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 04.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS |
| | SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT |
| | OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 05.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE |
| | WITH EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY OR |
| | THE VICINITY THEREOF (INCLUDING STREETS, ROADS, FIRE |
| | LANES). |
| | |
| | 06.PROVIDE THE OCCUPANT LOAD , AS IN THE NUMBERS OF |
| | PERSONS FOR WHOM MEANS OF EGRESS AND OTHER PROVISIONS |
| | ARE REQUIRED. |
| | |
| | 07.PLEASE SHOW TRAVEL DISTANCE TO EXITS ON THE LIFE |
| | SAFETY PLAN SHEET. |
| | |
| | 08.ANY DOOR IN A REQUIRED MENS OF EGRESSFROM AN |
| | AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS |
| | SHALL BE PROVIDED WITH PANIC HARDWARE OR FIRE EXIT |
| | HARDWARE. |
| | |
| | 09.SPECIFY THE INTERIOR FINISH MATERIALS FOR THE NEW |
| | WALLS IN TERRMS OF CLASS A, CLASS B, OR CLASS C. |
| | |
| | 10.PLANS DON' T INDICATE IF THE PROJECT SITE IS FIRE |
| | SPRINKLERED.IF SO SPRINKLERED AND THERE IS A CAUSE |
| | FOR THIS SYSTEM TO BE ALTERED DUE TO THE SCOPE OF WORK, |
| | SEPARATE PLANS AND PERMIT WILL BE REQUIRED. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS |
| | ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |