Plan Review Notes
Plan Review Notes For Permit 07110584
Permit Number 07110584
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-11-29 14:49:06***DENIED***
  
 1) FIRE ALARM NOTES REFERENCE SPRINKLER EQUIPMENT,
 HOWEVER NO EQUIPMENT IS SHOWN ON DRAWINGS, FIRE ALARM
 LEGEND OR RISER. IF BUILDING IS EQUIPPED WITH AN
 AUTOMATIC FIRE SPRINKLER SYSTEM, PLEASE SHOW
 APPROPRIATE EQUIPMENT AND NOTE THAT THE FIRE ALARM IS
 REQUIRED TO BE UL CERTIFIED FOR CENTRAL STATION
 SERVICE. IF THERE IS NO SPRINKLER EQUIPMENT, REMOVE
 REFERENCE FROM NOTES.
  
 2) THE APPLICATION INDICATES SUITE #1 AND THE PLANS
 SHOW #4 & #5. PLEASE CORRELATE INFORMATION.
  
 3) PLEASE CLEARLY IDENTIFY REQUIRED MONITORING ON THE
 ALARM RISER.
  
 4) PLANS DON'T SHOW THE LOCATION OF THE FACP.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756