| 2007-12-06 14:53:34 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 07 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1) FBC-2004 SEC 424.2.6.6, OR FBCR-2004 |
| | SEC R4101.6.6 ENTRAPMENT PROTECTION FOR |
| | SUCTION INLETS. (DETAIL REQUIRED) |
| | |
| | 2) FBC-2004 424.2.6.6.2, OR FBCR-2004 |
| | SEC R4101.6.6.2 SHOW COMPLIANCE WITH |
| | ANSI/ASME A112.19.8M. PROVIDE MODEL |
| | NUMBER AND MANUF INFO FOR VAC LOCK. |
| | (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES) |
| | |
| | 3) FBC-2004424.2.6.6.3, OR FBCR-2004 |
| | SEC R4101.6.6.3 (1,2,3) ENTRAPMENT |
| | AVOIDANCE. (DETAIL REQUIRED) |
| | |
| | 4) FBC-2004 SEC. 424.2.7.1, OR FBCR-2004 SEC.R4101.7.1 |
| | POOL CIRCULATING PUMPS |
| | SHALL BE EQUIPPED ON THE INLET SIDE WITH |
| | AN APPROVED TYPE HAIR AND LINT STRAINER |
| | WHEN USED WITH A PRESSURE FIL- TER. |
| | (DETAIL OR ADD TO NOTES) |
| | |
| | 5) FBC-2004 SEC. 424.2.9, OR FBCR-2004 SEC. |
| | R4101.9 WATER SUPPLY, LOCAL ORD. |
| | #2853-95, BACKFLOW REQUIRED ON WATER |
| | SERVICE.(ADD TO NOTES) |
| | |
| | 6) FBC-2004 SEC. 424.2.12.1, OR |
| | FBCR-2004 SEC. R4101.12.1 PRESSURE |
| | TESTS. PER MANUFACTURE RECOMMENDATIONS, |
| | NO AIR TEST SHALL BE APPROVED FOR PVC |
| | PIPE AND FITTINGS. (ADD TO NOTES) |
| | |
| | 7) FBC-2004 SEC. 424.2.13.2, OR |
| | FBCR-2004 SEC.R4101.13.2 JOINTS AND |
| | CONNECTIONS, FBC PLMG SEC 605.21, PURPLE |
| | PRIMER REQUIRED ON PVC PIPING.(ADD TO |
| | NOTES) |
| | |
| | 8) FBC-2004 SEC. 424.2.14.1, OR |
| | FBCR-2004 SEC. R4101.14.1 SWIMMING POOL |
| | WATER HEATERS SHALL BEAR THE LABEL OF A |
| | RECOGNIZED TESTING AGENCY. (MANUFACTURE |
| | SHEETS REQUIRED, PLEASE SUBMIT) |
| | |
| | 9) FBC-2004 SEC. 424.2.14.2, OR |
| | FBCR-2004 SEC. R4101.14.2 WATER |
| | RETENTION, PROVIDE A POSITIVE MEANS OF |
| | RETAINING WATER IN THE HEATER WHEN PUMP |
| | IS SHUT OFF.(MANUFACTURE SHEETS |
| | REQUIRED, PLEASE SUBMIT) |
| | |
| | 10) FBC-2004 SEC. 424.2.14.4, OR |
| | FBCR-2004 SEC. R4101.14.4 CONNECTIONS, |
| | ALL WATER HEATING EQUIPMENT SHALL BE |
| | INSTALLED WITH FLANGES OR UNION |
| | CONNECTIONS ADJACENT TO THE HEATER. |
| | (ADD TO NOTES) |
| | |
| | 11) FBC-2004 SEC. 13-612.1.ABC.2.3.3 |
| | TIME CLOCKS SHALL BE INSTALLED ON |
| | PRIVATE POOLS. |
| | |
| | 12) SHEET 2 AND 3 ARE INDICATING TWO DIFFERENT VENT |
| | PIPE SIZES TO MEET THE 3 SECOND RELEASE PER |
| | *424.2.6.6.3. PLEASE CORRELATE THE VENT PIPE SIZES ON |
| | THE RESUBMITTAL. PER *106.1.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 13) FBC-2004 SEC. 424.6.6 OR FBC-2004 |
| | RESIDENTIAL SEC. R4101.6.6: ENTRAPMENT |
| | PROTECTION FOR SUCTION INLETS. PLEASE |
| | SUBMIT AN ENGINEERED TABLE FOR "VENT |
| | PIPE MAXIMUM LENGTH" INDICATING PUMP |
| | SIZES, AVERAGE FLOW, AND MAXIMUM LENGTH |
| | OF THE 1" OR 1-1/2" PVC VENT PIPE, FROM |
| | WHERE IT STARTS TO WHERE IT ENDS UP, |
| | COMPLYING WITH THE THREE SECOND RELEASE. |
| | |
| | END OF COMMENTS: |
| | |