 APPLICATION #07110567
 ELECTRICAL PLAN REVIEW
 5600 N. FLAGLER DRIVE
 12/4/07
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE
 NOTED.
  
 1} 408.30 GENERAL. ALL PANELBOARDS SHALL HAVE A RATING
 NOT LESS THAN THE MINIMUM FEEDER CAPACITY REQUIRED FOR
 THE LOAD CALCULATED IN ACCORDANCE WITH ARTICLE 220. THE
 130 AMP LOAD CALCULATED ON THE PANEL EXCEEDS THE 125
 AMP PANEL RATING.
  
 2} THE INSTA HOT SHOWN ON THE PLAN IS NOT ON THE PANEL
 SCHEDULE OR IN THE LOAD CALCULATION. 220.12, 220.14,
 220.83. (SEE THESE ARTICLES FOR THE CORRECT
 CALCULATION. 220.30 IS AN ARTICLE FROM 2004 CODE,
 REMOVE FROM PLAN).
  
 3} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), AND BE GFI PROTECTED PER 210.8(A)
 (1). THIS CIRCUIT IS NOT ON THE PANEL SCHEDULE.
  
 4} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. THE ?BAR? IS
 A PENINSULAR FOR THE KITCHEN WHOSE COUNTERTOP
 RECEPTACLES MUST COMPLY WITH 210.8(A)(6) AS WELL.
 GFCI.
  
 5} THE COUNTERTOP BEING INSTALLED MUST ALLOW 3?
 CLEARANCE FROM THE EXISTING PANEL PER 110.26.
  
 6} PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE
 BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE
 CIRCUIT THAT MAY ENERGIZE THE FRAMING. SEE ARTICLE.
 PLEASE PUT A NOTE ON THE PLAN FOR CLARITY IN THE
 FIELD.
  
 THE TITLE BLOCK CONTAINS THE ADDRESS OF THE PROJECT
 REQUIRED BY 106.3.1 FBC, BUT INCLUDES THE WORD
 ?ADDITION?. AS THIS DOES NOT APPEAR TO BE AN ADDITION,
 CLARIFY. 301.5 FBC EXISTING BUILDING CODE. THE DESIGN
 PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF THE
 EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE
 PLAN.
  