| 2007-12-04 15:02:12 | |
| | |
| | APPLICATION #07110567 |
| | ELECTRICAL PLAN REVIEW |
| | 5600 N. FLAGLER DRIVE |
| | 12/4/07 |
| | WEST PALM BEACH, FL. |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE |
| | NOTED. |
| | |
| | 1} 408.30 GENERAL. ALL PANELBOARDS SHALL HAVE A RATING |
| | NOT LESS THAN THE MINIMUM FEEDER CAPACITY REQUIRED FOR |
| | THE LOAD CALCULATED IN ACCORDANCE WITH ARTICLE 220. THE |
| | 130 AMP LOAD CALCULATED ON THE PANEL EXCEEDS THE 125 |
| | AMP PANEL RATING. |
| | |
| | 2} THE INSTA HOT SHOWN ON THE PLAN IS NOT ON THE PANEL |
| | SCHEDULE OR IN THE LOAD CALCULATION. 220.12, 220.14, |
| | 220.83. (SEE THESE ARTICLES FOR THE CORRECT |
| | CALCULATION. 220.30 IS AN ARTICLE FROM 2004 CODE, |
| | REMOVE FROM PLAN). |
| | |
| | 3} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE |
| | PER 210.11(C) (3), AND BE GFI PROTECTED PER 210.8(A) |
| | (1). THIS CIRCUIT IS NOT ON THE PANEL SCHEDULE. |
| | |
| | 4} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH |
| | 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. THE ?BAR? IS |
| | A PENINSULAR FOR THE KITCHEN WHOSE COUNTERTOP |
| | RECEPTACLES MUST COMPLY WITH 210.8(A)(6) AS WELL. |
| | GFCI. |
| | |
| | 5} THE COUNTERTOP BEING INSTALLED MUST ALLOW 3? |
| | CLEARANCE FROM THE EXISTING PANEL PER 110.26. |
| | |
| | 6} PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE |
| | BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE |
| | CIRCUIT THAT MAY ENERGIZE THE FRAMING. SEE ARTICLE. |
| | PLEASE PUT A NOTE ON THE PLAN FOR CLARITY IN THE |
| | FIELD. |
| | |
| | THE TITLE BLOCK CONTAINS THE ADDRESS OF THE PROJECT |
| | REQUIRED BY 106.3.1 FBC, BUT INCLUDES THE WORD |
| | ?ADDITION?. AS THIS DOES NOT APPEAR TO BE AN ADDITION, |
| | CLARIFY. 301.5 FBC EXISTING BUILDING CODE. THE DESIGN |
| | PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF |
| | ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF THE |
| | EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE |
| | PLAN. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |