| 2007-12-01 09:45:49 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07110567 |
| | ADD: 5600 N. FLAGLER DR. #2409 |
| | CONT: COLBURN CONST. INC. |
| | TEL: (561)805-7165 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | 12/1/07 |
| | |
| | 1A)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 1B) PLEASE SUBMIT 2 COPIES OF ALL, PLANS, REPORTS, |
| | PRODUCT APPROVALS FOR REVIEW FOR PERMIT. |
| | 106.1* /2004 SUBMITTAL DOCUMENTS WEST PALM BEACH |
| | ADMINISTRATIVE CODE. |
| | |
| | 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 |
| | DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| | THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| | SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS |
| | A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | |
| | |
| | |
| | 2)2004 FBC EXISTING |
| | 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 303, 304 AND 305 OF THIS CODE. THIS PROJECT |
| | APPEARS TO BE A LEVEL 2. |
| | |
| | 3)THE CLAIMED VALUATION OF BUILDING, ALTERATION, |
| | STRUCTURE, ELECTRICAL, MECHANICAL OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDERESTIMATED ON THE APPLICATION. |
| | VALUATION SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR |
| | FINISH, ARCHITECTURAL AND DESIGN FEES EXCLUDING LAND. |
| | OUR VALUATION REFERENCE IS ICC (BVD), MARSHALL-SWIFT |
| | AND MEANS COST ANALYSIS SERVICES PER 108.3 FBC* |
| | |
| | 4) 106.3.3* PRODUCT APPROVALS- THOSE PRODUCTS THAT ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. PROVIDE THE |
| | PRODUCT APPROVALS FOR THE SLIDING GLASS DOORS AND THE |
| | GLASS BLOCK. PROVIDE BUILDING HEIGHT ON THE PLAN. |
| | DESIGN PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED |
| | TO BE DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE |
| | DONE BY AN ENGINEER. DOCUMENTS PREPARED BY AN ENGINEER |
| | AND SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED SEALED |
| | ORIGINALS FAC61G15-23.002. THIS REFERS TO THE SLIDING |
| | GLASS DOORS. |
| | |
| | 5)FBC 907.2.10.1.2 SINGLE OR MULTIPLE-STATION SMOKE |
| | ALARMS SHALL BE INSTALLED INSIDE AND OUTSIDE EACH ROOM |
| | USED FOR SLEEPING PURPOSES. SEE R313 FBC RESIDENTIAL. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |