Plan Review Notes
Plan Review Notes For Permit 07110567
Permit Number 07110567
Review Stop B
Sequence Number 1
Notes
Date Text
2007-12-01 09:45:49 
 BUILDING PLAN REVIEW
 PERMIT: 07110567
 ADD: 5600 N. FLAGLER DR. #2409
 CONT: COLBURN CONST. INC.
 TEL: (561)805-7165
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
 12/1/07
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) PLEASE SUBMIT 2 COPIES OF ALL, PLANS, REPORTS,
 PRODUCT APPROVALS FOR REVIEW FOR PERMIT.
 106.1* /2004 SUBMITTAL DOCUMENTS WEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
  
  
  
 2)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE. THIS PROJECT
 APPEARS TO BE A LEVEL 2.
  
 3)THE CLAIMED VALUATION OF BUILDING, ALTERATION,
 STRUCTURE, ELECTRICAL, MECHANICAL OR PLUMBING SYSTEMS
 APPEARS TO BE UNDERESTIMATED ON THE APPLICATION.
 VALUATION SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, ARCHITECTURAL AND DESIGN FEES EXCLUDING LAND.
 OUR VALUATION REFERENCE IS ICC (BVD), MARSHALL-SWIFT
 AND MEANS COST ANALYSIS SERVICES PER 108.3 FBC*
  
 4) 106.3.3* PRODUCT APPROVALS- THOSE PRODUCTS THAT ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL. PROVIDE THE
 PRODUCT APPROVALS FOR THE SLIDING GLASS DOORS AND THE
 GLASS BLOCK. PROVIDE BUILDING HEIGHT ON THE PLAN.
 DESIGN PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED
 TO BE DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE
 DONE BY AN ENGINEER. DOCUMENTS PREPARED BY AN ENGINEER
 AND SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED SEALED
 ORIGINALS FAC61G15-23.002. THIS REFERS TO THE SLIDING
 GLASS DOORS.
  
 5)FBC 907.2.10.1.2 SINGLE OR MULTIPLE-STATION SMOKE
 ALARMS SHALL BE INSTALLED INSIDE AND OUTSIDE EACH ROOM
 USED FOR SLEEPING PURPOSES. SEE R313 FBC RESIDENTIAL.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]