| Plan Review Notes For Permit 07110550 |
| Permit Number |
07110550 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-02-25 16:15:32 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1.SEE PREVIOUS CORRECTION LIST.TWO SETS REQUIRED. | | | ONLY ONE INSTALLATION SCHEDULE WAS PROVIDED. | | | | | | 2.SHUTTER CONNECTION MOUNTING TYPE SHOULD CORRELATE | | | WITH THE ANCHOR SCHEDULES ON THE PRODUCT APPROVAL; IN | | | THIS CASE, A THROUGH L.PLEASE REVISE INSTALLATION | | | SCHEDULE. | | | | | | 3.NOTE THAT A 2" EDGE DISTANCE REQUIRES A FACTOR OF | | | .5, SEE SHEET 11.IT DOES NOT APPEAR THAT ANCHOR | | | SPACING SPECIFIED IS COMPLIANT AS THIS FACTOR HAS NOT | | | BEEN APPLIED. | | | | | | 4.SPANS FOR ACCORDION SHUTTERS EQUAL BLADE LENGTH. | | | REVISE SPANS; ALL ARE TOO SMALL BY APPROXIMATELY 2'. | | | | | | | | | | | | | | | |
|