Notes
Date Text
2008-02-25 16:15:32****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.SEE PREVIOUS CORRECTION LIST.TWO SETS REQUIRED.
 ONLY ONE INSTALLATION SCHEDULE WAS PROVIDED.
  
 2.SHUTTER CONNECTION MOUNTING TYPE SHOULD CORRELATE
 WITH THE ANCHOR SCHEDULES ON THE PRODUCT APPROVAL; IN
 THIS CASE, A THROUGH L.PLEASE REVISE INSTALLATION
 SCHEDULE.
  
 3.NOTE THAT A 2" EDGE DISTANCE REQUIRES A FACTOR OF
 .5, SEE SHEET 11.IT DOES NOT APPEAR THAT ANCHOR
 SPACING SPECIFIED IS COMPLIANT AS THIS FACTOR HAS NOT
 BEEN APPLIED.
  
 4.SPANS FOR ACCORDION SHUTTERS EQUAL BLADE LENGTH.
 REVISE SPANS; ALL ARE TOO SMALL BY APPROXIMATELY 2'.
  
  
  
  
  