Plan Review Notes
Plan Review Notes For Permit 07110549
Permit Number 07110549
Review Stop B
Sequence Number 1
Notes
Date Text
2007-11-26 15:59:39****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR
 PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT, FBC*106.TWO SETS REQUIRED.
  
 2.PLEASE NOTE EXISTING CONDITIONS (TYPE OF WINDOW)
 FOR BEDROOMS, FBC R310, FBC EB 505.1.YOU CANNOT
 REDUCE THE CLEAR OPENING SIZE BY MORE THAN 5%.
  
 3.ON THE INSTALLATION SCHEDULE, THE CONNECTION
 MOUNTING TYPE SHOULD CORRELATE WITH THE ANCHOR
 SCHEDULE, WHICH IS MOST LIKELY C1 THROUGH C5.SEE
 COMMENT #4.
  
 4.THE PRODUCT APPROVAL FOR THE SHUTTERS DID NOT PRINT
 PROPERLY.THE TOP OF THE ANCHOR SCHEDULE DOES NOT
 APPEAR, AND THIS INFORMATION IS REQUIRED FOR YOU TO
 COMPLETE THE INSTALLATION SCHEDULE AND FOR CODE
 COMPLIANCE TO BE DETERMINED.
  
 5.FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED IN
 ADDITION TO THE NOA PROVIDED, FAC9B72,
 WWW.FLORIDABUILDING.ORG.IF A FLORIDA STATE PRODUCT
 APPROVAL IS UNAVAILABLE, PLEASE ADVISE.
  