| Date |
Text |
| 2008-02-26 16:43:19 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED 4TH TIME: |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | THE PREVIOUS PLUMBING PLAN REVIEW COMMENTS AS WELL AS |
| | THE DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUTY. |
| | NOTE: THERE WERE NO DESIGNER COMMENT RESPONSES TO THE |
| | PREVIOUS PLUMBING PLAN REVIEW. |
| | |
| | 1. **OK** COMMENT ADDRESSED. |
| | |
| | 2. **OK** COMMENT ADDRESSED. |
| | |
| | 3. **OK** COMMENT ADDRESSED. |
| | |
| | 4. **OK** RESPONSE NOTED. |
| | |
| | 5. **OK** RESPONSE NOTED, COMMENT ADDRESSED. |
| | |
| | 6. **OK** COMMENT ADDRESSED. |
| | |
| | 7. **OK** COMMENT ADDRESSED. |
| | |
| | 8.AT A MINIMUM THE SANITARY RISER AND PLUMBING FLOOR |
| | PLAN ON SHEET P-100 SHALL REFLECT THE FLOOR PLAN OF |
| | REVISED SHEET A-105. PER FBC PLUMBING SECTION *701.1 |
| | SCOPE.** |
| | |
| | ****NO COMMENT RESPONSE****THE RESUBMITTED SHEET |
| | P-100 HAS NOT BEEN REVISED TO REFLECT THE REVISED FLOOR |
| | PLAN OF SHEET A-102 AND SHEET A-105, RENOVATED SHOWROOM |
| | - RESTROOM FLOOR PLAN. PLEASE CORRELATE AND CORRECT ON |
| | THE NEXT RESUBMITTAL. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |