| 2007-12-11 15:33:18 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET A-100 OCCUPANCY LOAD & TOILET FIXTURE |
| | REQUIREMENTS: PER TABLE 403.1, |
| | CLASSIFICATION-BUSSINESS, PLEASE CORRECT THE FIXTURE |
| | PER SEX AS FOLLOWS AND CHANGE THE WORD "FUTURE" TO |
| | "FIXTURE" |
| | |
| | **WATER CLOSETS= 1 PER 25 FOR THE FIRST 50 AND 1 PER |
| | 50 FOR THE REMAINDER EXCEEDING 50. |
| | |
| | **LAVATORIES= 1 PER 40 FOR THE FIRST 50 AND 1 PER 80 |
| | FOR THE REMAINDER EXCEEDING 50. |
| | |
| | **DRINKING FOUNTAIN= 1 PER 100. |
| | |
| | 2. SHEET A-101 FLOOR PLAN: PER THE FLOOR PLAN THERE IS |
| | NOT A DRINKING FOUNTAIN INDICATED. PER TABLE *403.1 ONE |
| | IS REQUIRED. PLEASE CLARIFY IF ONE IS EXISTING OR A NEW |
| | ONE IS GOING TO BE PROVIDED ON THE RESUBMITTAL. |
| | |
| | 3. SHEET A-101 FLOOR PLAN, MEN ROOM NUMBER A105: THE |
| | TOILET STALL ROOM DOOR SHALL NOT SWING INTO THE CLEAR |
| | FLOOR SPACE OF ANY FIXTURE. THE STALL DOOR IS SWINGING |
| | INTO THE CLEAR FLOOR SPACE OF THE LAVATORY.PER |
| | *11-4.17.5 DOORS. |
| | |
| | 4. SHEET A-101 FLOOR PLAN, MEN ROOM NUMBER A105: DO TO |
| | THE NEW RECONFIGURATION OF THE MENS ROOM AND STALL |
| | DOORS SWINGING INTO CLEAR FLOOR SPACE PLEASE COMPLY |
| | WITH THE FOLLOWING 11-4.17.3 SIZE AND ARRANGEMENT. |
| | (1)THE STANDARD ACCESSIBLE RESTROOM STALL SHALL |
| | CONTAIN AN ACCESSIBLE LAVATORY WITHIN IT, THE SIZE OF |
| | SUCH LAVATORY TO BE NOT LESS THAN 19 INCHES WIDE BY 17 |
| | INCHES (483 MM BY 432 MM) DEEP, NOMINAL SIZE, AND WALL |
| | MOUNTED. THE LAVATORY SHALL BE MOUNTED SO AS NOT TO |
| | OVERLAP THE CLEAR FLOOR SPACE AREAS REQUIRED BY SECTION |
| | 11-4.17 [SEE FIGURE 30 (A) AND FIGURE 30 (E)] AND TO |
| | COMPLY WITH SECTION 11-4.19 OF THE CODE. SUCH |
| | LAVATORIES SHALL BE COUNTED AS PART OF THE REQUIRED |
| | FIXTURE COUNT FOR THE BUILDING. |
| | (2)THE ACCESSIBLE WATER CLOSET SHALL BE LOCATED IN |
| | THE CORNER, DIAGONAL TO THE DOOR. |
| | |
| | 5. SHEET A-101 FLOOR PLAN ROOM NUMBER A101: THIS ROOM |
| | IS NOT COMPLIANT PER THE FOLLOWING. |
| | 11-4.2.3 WHEELCHAIR TURNING SPACE. |
| | THE SPACE REQUIRED FOR A WHEELCHAIR TO MAKE A |
| | 180-DEGREE TURN IS A CLEAR SPACE OF 60 INCHES (1525 MM) |
| | DIAMETER [SEE FIGURE 3 (A)]. |
| | |
| | 6. SHEET A-105 MENS TOILET DETAIL #3 & #4: THE WALL |
| | TILE IS NOT HIGH ENOUGH FOR THE URINAL PER THE |
| | FOLLOWING. |
| | [B] 419.3 SURROUNDING MATERIAL. |
| | WALL AND FLOOR SPACE TO A POINT 2 FEET (610 MM) IN |
| | FRONT OF A URINAL LIP AND 4 FEET (1219 MM) ABOVE THE |
| | FLOOR AND AT LEAST 2 FEET (610 MM) TO EACH SIDE OF THE |
| | URINAL SHALL BE WATERPROOFED WITH A SMOOTH, READILY |
| | CLEANABLE, NONABSORBENT MATERIAL. |
| | |
| | |
| | 7. SHEET A-105 MENS TOILET DETAIL #1 & #2: PAINTED |
| | WALLS FOR THE WATER CLOSET IS NOT COMPLIANT PER THE |
| | FOLLOWING. |
| | 1210.2 WALLS. |
| | WALLS WITHIN 2 FEET (610 MM) OF URINALS AND WATER |
| | CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT |
| | SURFACE, TO A HEIGHT OF 4 FEET (1219 MM) ABOVE THE |
| | FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS, THE |
| | MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE THAT IS |
| | NOT ADVERSELY AFFECTED BY MOISTURE. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |