| Plan Review Notes For Permit 07110548 |
| Permit Number |
07110548 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-12-12 17:45:05 | *****UNSAT***** | | | | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2.BUILDINGS OR PORTIONS OF BUILDINGS SHALL BE | | | PERMITTED TO BE OCCUPIED DURING CONSTRUCTION, REPAIR, | | | ALTERATIONS, OR ADDITIONS ONLY WHERE REQUIRED MEANS OF | | | EGRESS AND REQUIRED FIRE PROTECTION FEATURES ARE IN | | | PLACE AND CONTINUOUSLY MAINTAINED. | | | | | | 3.PLEASE INDICATE IF THE BUILDING IS FIRE | | | SPRINKLERED.IF PROJECT SCOPE OF WORK HAS CAUSE FOR | | | THE SPRINKLER AND/OR FIRE ALARM SYSTEM TO BE REMODELED, | | | SEPARATE PLANS AND PERMIT WILL BE REQUIRED. | | | | | | 4.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 5.SPECIFY THE NEW INTERIOR WALL CEILING FINISH | | | MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | SPECIFY THE NEW INTERIOR FLOOR FINISH IN TERMS OF CLASS | | | I OR CLASS II. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | INDICATING WHERE ON THE PLAN EACH ITEM HAS BEEN | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|