| Plan Review Notes For Permit 07110531 |
| Permit Number |
07110531 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-12-11 08:45:25 | DENIED; | | | 1. PAGE A-6.0 BREAK SINK DETAIL. NO CABINET DOORS | | | PERMITED. SEE FBC BUILDING CHAPTER 11 SECTION 11-4.24.3 | | | KNEE CLEARANCE UNDER SINK.SHOW ON DETAIL ALL | | | MEASUREMENTS REQUIRE TO COMPLY WITH SECTIONS 11-4.24.1 | | | THRU 11-4.24.7. | | | 2. DRINKING FOUNTAIN ON FLOOR PLAN PAGE A-1.1. | | | 3. WATER HEATER ON WATER RISER DIAGRAM SHOW THE | | | TERMINATION POINTS FOR RELIEF LINE AND PAN DRAIN. SEE | | | FBC-PLUMBING SECTIONS 504.6 AND 504.7.2. | | | 4. SHOW THERMAL EXPANTION CONTROL TO BE USED , SEE | | | SECTION 607.3. SHOW ON PLANS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|