2007-12-11 08:45:25DENIED;
 1. PAGE A-6.0 BREAK SINK DETAIL. NO CABINET DOORS
 PERMITED. SEE FBC BUILDING CHAPTER 11 SECTION 11-4.24.3
 KNEE CLEARANCE UNDER SINK.SHOW ON DETAIL ALL
 MEASUREMENTS REQUIRE TO COMPLY WITH SECTIONS 11-4.24.1
 THRU 11-4.24.7.
 2. DRINKING FOUNTAIN ON FLOOR PLAN PAGE A-1.1.
 3. WATER HEATER ON WATER RISER DIAGRAM SHOW THE
 TERMINATION POINTS FOR RELIEF LINE AND PAN DRAIN. SEE
 FBC-PLUMBING SECTIONS 504.6 AND 504.7.2.
 4. SHOW THERMAL EXPANTION CONTROL TO BE USED , SEE
 SECTION 607.3. SHOW ON PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695