| Plan Review Notes For Permit 07110531 |
| Permit Number |
07110531 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-12-12 12:44:53 | ***DENIED*** | | | | | | 1) MERCANTILE OCCUPANCY IS REFERENCED FOR INTERIOR WALL | | | AND CEILING FINISHES, AND THE OCCUPANT LOAD IS BASED ON | | | BUSINESS. PLEASE CORRELATE ALL INFORMATION USING THE | | | CORRECT OCCUPANCY CLASSIFICATION FOR THIS SPACE. | | | | | | 2) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION. | | | | | | 3) THE BREAKROOM EXIT DOOR SHALL NOT BE OBSTRUCTED BY | | | TYPICAL BREAKROOM FURNITURE. | | | | | | 4) SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED FOR | | | FIRE SPRINKLER AND FIRE ALARM REMODEL IF APPLICABLE. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|