| Date |
Text |
| 2007-11-20 11:56:19 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | ROOFING PERMIT; ONLY CHECKED ITEMS APPLY |
| | |
| | _XX_1.)EFFECTIVE OCTOBER 1, 2007, SECONDARY WATER |
| | BARRIER REQUIRED FS553.844(5)(A). PROVIDE |
| | INFORMATION (PRODUCT APPROVAL OR SPECIFICATIONS) TO |
| | SHOW HOW YOU WILL COMPLY WITH THIS REQUIREMENT. |
| | |
| | INFORMATION IS AVAILABLE AT WWW.BOAF.NET. |
| | |
| | PLEASE NOTE THAT AN ADDITIONAL CAP SHEET CAN BE USED TO |
| | COMPLY WITH THIS REQUIREMENT.FOR THE SYSTEM YOU |
| | CHOSE, SYSTEM TYPE E, TAMKO MODIFIED OVER WOOD, YOU |
| | HAVE HIGHLIGHTED TAM-PLY IV AS AN OPTIONAL PLY SHEET. |
| | EITHER AWAPLAN VERSA-SMOOTH OR AWAPLAN VERSAFLEX CAN BE |
| | USED AS THE OPTIONAL PLY SHEET AND, AS THEY ARE BOTH |
| | APPROVED CAP SHEETS, CAN BE USED AS THE SECONDARY WATER |
| | BARRIER IN LIEU OF TAPING THE DECK OR PROVIDING A FULL |
| | DECK MODIFIED COVERING.THIS ADDITIONAL CAP SHEET CAN |
| | BE USED EITHER IN ADDITION TO OR IN LIEU OF THE TAM-PLY |
| | IV. |
| | |
| | WHEN RESUBMITTING, PLEASE SUMMARIZE THE SYSTEM YOU |
| | PROPOSE BY ITEMIZING EACH PLY, INCLUDING TREATMENT OF |
| | THE DECK IF YOU CHOOSE ONE OF THOSE OPTIONS AS THE |
| | SECONDARY WATER BARRIER RATHER THAN AN ADDITIONAL PLY. |
| | PLEASE CONTACT ME IF YOU NEED ASSISTANCE. |
| | |
| | ____2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING |
| | INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY; |
| | MEAN ROOF HEIGHT, ROOF PITCH, ROOF DECK TYPE, AREA OF |
| | EACH ROOF TYPE |
| | |
| | _XX_3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| | REQUIRED IN ADDITION TO THE EVALUATION REPORT |
| | SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG |
| | |
| | ____4.)FOR THE FLAT DECK, SELECT THE APPROVED |
| | ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER |
| | YOU ARE USING IF THE OPTIONS HAVE DIFFERENT PRESSURE |
| | LIMITATIONS. |
| | |
| | _XX_5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED |
| | FASTENING FOR CORNER AND PERIMETER ZONES.THIS IS TO |
| | BE EITHER WRITTEN ON THE PRODUCT APPROVAL OR SUBMITTED |
| | ON LETTERHEAD, TWO SETS (NOT WRITTEN ON THE RESUB |
| | SHEET). |
| | |
| | ____ 6.)ON THE TILE PRODUCT APPROVAL, INDICATE WHICH |
| | METHOD OF ATTACHMENT YOU ARE USING.IF YOU SELECT FOAM |
| | ADHESIVE, PRODUCT APPROVALS REQUIRED FAC9B72. |
| | |
| | ____ 7.)SEE PRODUCT LIMITATION #7.CALCULATIONS |
| | PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF |
| | CONSULTANT REQUIRED FOR ENHANCED FASTENING. |
| | |