| Plan Review Notes For Permit 07110497 |
| Permit Number |
07110497 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-11-26 16:03:33 | | | | | | | APPLICATION # 07110497 | | | ELECTRICAL PLAN REVIEW | | | 3501 ELECTRONICS WAY | | | 11/26/07 | | | WEST PALM BEACH, FL. | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE | | | NOTED. | | | | | | 1} PER 700.12(F)(4)??THE BRANCH CIRCUIT FEEDING THE | | | UNIT EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS THAT | | | SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED | | | AHEAD OF ANY LOCAL SWITCHES.? INDICATE SAME ON PLANS. | | | | | | 2} PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON THE | | | PLANS PER 106.1.1 FBC AS AMENDED. | | | | | | 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2, ALL | | | SHEETS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|