| Plan Review Notes For Permit 07110478 |
| Permit Number |
07110478 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2008-06-25 10:44:45 | 2004 FBC W/2007 REVISIONS | | | REVISION TO ADD EXTERIOR DOOR TO ADDITION | | | | | | DENIED BY BUILDING | | | | | | 1) THE DRAWINGS ARE REQUIRED TO HAVE A TITLE BLOCK | | | CONTAINING ALL OF THE INFORMATION REQUIRED BY FLORIDA | | | STATUTES AND FAC 61G15-23.002. | | | | | | 2) SUBMIT TWO SIGNED, SEALED AND DATED COPIES OF | | | REVISED DRAWINGS. FBC 106.1 | | | | | | 3) IN ADDITION TO THE FLOOR PLANS, SUBMIT TWO SIGNED | | | AND SEALED COPIES OF A REVISED ELEVATION SHOWING | | | LOCATION OF THE NEW DOOR. FBC R301.2.1 AND DCA RULE | | | 9B-72. | | | | | | 4) IN ADDITION TO THE FLOOR PLANS, SUBMIT TWO SIGNED | | | AND SEALED COPIES OF A REVISED ROOF FRAMING PLAN | | | SPECIFYING THE LINTEL THAT WILL BE USED ABOVE THE DOOR | | | OPENING. FBC R606.8 | | | | | | 5) THE PRESSURES SPECIFIED ON THE REVISION ARE TOO LOW | | | AS THE DOOR APPEARS TO BE LOCATED IN WALL ZONE 5. | | | PLEASE CORRECT. FBC R301.2.1 AND FIGURE R301.2(8). | | | | | | 6) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE | | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | THE PRODUCT APPROVALS FOR THE DOOR HAS NOT BEEN | | | APPROVED IN WRITING BY THE ENGINEER. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|