| Plan Review Notes For Permit 07110470 |
| Permit Number |
07110470 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-12-04 16:25:37 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 07 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | GAS PLAN REVIEW: | | | DENIED: | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | **NOTE: CORRESPONDING LENGTHS ARE NOT INDICATED FOR | | | ALL CUT SECTIONS OF PIPE. PLEASE CORRELATE THE GAS | | | RISER WITH THE INDICATED LONGEST RUN OF 62' ON THE | | | RESUBMITTAL. | | | | | | 2. FBC-2004 CHAPTER 1,SECTION 106.3.4.3: | | | THE PERSON RESPONSIBLE FOR THE DESIGN OF | | | THE DRAWING SHALL CLEARLY PRINT AND SIGN | | | NAME, AND ALSO DATE DRAWING. PLEASE DO | | | THIS PRIOR TO RESUBMITTING. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|