Plan Review Notes
Plan Review Notes For Permit 07110470
Permit Number 07110470
Review Stop G
Sequence Number 1
Notes
Date Text
2007-12-04 16:25:37PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 07 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 **NOTE: CORRESPONDING LENGTHS ARE NOT INDICATED FOR
 ALL CUT SECTIONS OF PIPE. PLEASE CORRELATE THE GAS
 RISER WITH THE INDICATED LONGEST RUN OF 62' ON THE
 RESUBMITTAL.
  
 2. FBC-2004 CHAPTER 1,SECTION 106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 END OF COMMENTS:
  