2008-02-04 09:13:58 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PROVIDE LOAD CALCULATIONS PER 220.83 INCLUDING
 EXISTING AND ADDED LOADS.106.3.5.4(8) FBC AS AMENDED.
  
 2} LOCATE THE NEW 125 AMP PANEL ON THE PLANS SO THAT
 COMPLIANCE WITH 230.70, 225.32 MAY BE REVIEWED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  