 APPLICATION #07110460
 ELECTRICAL PLAN REVIEW
 10301 HERONWOOD LANE
 11/20/07
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE
 NOTED.
 ALL COMMENTS RELATE TO SHEET E1.0, UNLESS OTHERWISE
 NOTED.
  
 1} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III,
 STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED.
 THIS IS TO VERIFY THE TOTAL LOAD IS IN COMPLIANCE WITH
 220.83, TOTAL LOAD DOES NOT EXCEED THE SERVICE RATING.
  
 2} THE RISER DIAGRAM FEEDERS AND PANEL RATING ARE NOT
 CONSISTENT WITH THE PLANS. THE PLAN INDICATES A 60 AMP
 PANEL, THE RISER A 50 AMP. THE 6/0 FEEDERS INDICATED ON
 THE RISER DO NOT CORRELATE WITH AWG SIZES IN THE NEC.
  
 3} CIRCUIT #9 ON THE PANEL SCHEDULE INDICATES EXTERIOR
 RECEPTACLES ON THE SAME CIRCUIT WITH THE BATH IN
 VIOLATION OF 210.11(C)(3).
  
 4} THE DISCONNECT FOR THE A/C UNIT DOES NOT COMPLY WITH
 110.26 CLEARANCE REQUIREMENTS. INDICATE IF THIS IS A
 NEW OR RELOCATED SYSTEM.
  
 PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH
 CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM
 SEPARATELY TO EXPEDITE THE REVIEW PROCESS. RESPOND TO
 REVIEW COMMENTS IN WRITING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718