| | APPLICATION #07110460 |
| | ELECTRICAL PLAN REVIEW |
| | 10301 HERONWOOD LANE |
| | 11/20/07 |
| | WEST PALM BEACH, FL. |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE |
| | NOTED. |
| | ALL COMMENTS RELATE TO SHEET E1.0, UNLESS OTHERWISE |
| | NOTED. |
| | |
| | 1} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III, |
| | STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED. |
| | THIS IS TO VERIFY THE TOTAL LOAD IS IN COMPLIANCE WITH |
| | 220.83, TOTAL LOAD DOES NOT EXCEED THE SERVICE RATING. |
| | |
| | 2} THE RISER DIAGRAM FEEDERS AND PANEL RATING ARE NOT |
| | CONSISTENT WITH THE PLANS. THE PLAN INDICATES A 60 AMP |
| | PANEL, THE RISER A 50 AMP. THE 6/0 FEEDERS INDICATED ON |
| | THE RISER DO NOT CORRELATE WITH AWG SIZES IN THE NEC. |
| | |
| | 3} CIRCUIT #9 ON THE PANEL SCHEDULE INDICATES EXTERIOR |
| | RECEPTACLES ON THE SAME CIRCUIT WITH THE BATH IN |
| | VIOLATION OF 210.11(C)(3). |
| | |
| | 4} THE DISCONNECT FOR THE A/C UNIT DOES NOT COMPLY WITH |
| | 110.26 CLEARANCE REQUIREMENTS. INDICATE IF THIS IS A |
| | NEW OR RELOCATED SYSTEM. |
| | |
| | PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH |
| | CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM |
| | SEPARATELY TO EXPEDITE THE REVIEW PROCESS. RESPOND TO |
| | REVIEW COMMENTS IN WRITING. |
| | |