| 2007-12-10 13:03:49 | RESIDENTIAL ADDITION BUILDING REVIEW CHECKLIST. REVIEW |
| | DONE UNDER FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD |
| | (561)233-5115) TO VERIFY IF IMPACT FEES ARE DUE. BRING |
| | BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE |
| | DUE. |
| | |
| | 2- SHEET T1.0: |
| | A) SPECIFY ATTIC LIVE LOAD AS REQUIRED BY TABLE |
| | R301.5 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | B) CODE TO BE REFERENCED IS FBC 2004 WITH 2007 |
| | REVISIONS, NOT 2006. UPDATE AS REQUIRED. |
| | |
| | C) COMPONENTS & CLADDING DESIGN WIND PRESSURES DON'T |
| | MATCH THE DESIGN PRESSURES SPECIFIED ON SHEET A3.0. |
| | REVISE AS REQUIRED TO MATCH. |
| | |
| | D) CONSULTING ENGINEER "STRUCTURAL SYSTEMS, INC" TO |
| | SIGN AND SEAL DRAWINGS AS REQUIRED BY CHAPTER 471 |
| | FLORIDA STATUTE AND SEC. 61G15-23.002(2) OF FLORIDA |
| | ADMINISTRATIVE CODE. |
| | |
| | E) REVISE MASONRY NOTE ON STRUCTURAL NOTES AND ON |
| | CONCRETE UNIT MASONRY NOTE F.SEE SEC. R606.4 OF 2004 |
| | FLORIDA RESIDENTIAL CODE REGARDING THE MINIMUM MASONRY |
| | UNIT ALLOWABLE STRESS. |
| | |
| | F) UPDATE THERMAL MOISTURE PROTECTION NOTE A. SEE |
| | CHAPTER 13 FBC 2004 FOR CORRECT REFERENCE TO BE USED. |
| | |
| | 3- PROVIDE SOIL TEST REPORT.SEC. R401.4 OF 2004 |
| | FLORIDA RESIDENTIALCODE.TWO COPIES WITH ORIGINAL |
| | SIGNATURE AND SEAL. AND, ENGINEERING FIRM CERTIFICATE |
| | OF AUTHORIZATION NUMBER. SEC. 61G15-23.002(2) OF |
| | FLORIDA ADMINISTRATIVE CODE. |
| | |
| | 4- DESIGNEROF RECORD TO SPECIFY ROOF TILE FASTENING. |
| | SEESEC. 106.1.1.2 CITY AMENDMENTS TO FBC 2004. IF |
| | USING POLYFOAM, THEN PROVIDE PRODUCT APPROVAL AS |
| | REQUIRED BY DCA RULE 9B-72. |
| | IN ADDITION, MAKE SURE THAT TILE ADHESIVE IS TESTED AND |
| | APPROVED TO BE USED WITH GRACE ICE UNDERLAYMENT, WHICH |
| | IS THE TYPE OF UNDERLAYMENT THAT WAS SUBMITTED WITH |
| | THIS PACKAGE. PROVIDE TECHNICAL INFORMATION AS REQUIRED |
| | TO SHOW COMPATIBILITY WITH THE PROPOSED INSTALLATION. |
| | ON THE OTHER HAND, IF USING NAILS OR SCREWS, THEN |
| | CLEARLY SPECIFY TYPE AND NUMBER TO VERIFY COMPLIANCE |
| | WITH THE UPLIFT RESISTANCE SHOWN ON THE PRODUCT |
| | APPROVAL. |
| | |
| | 5- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| | 9B-72 FOR: |
| | A) FIXED WINDOW SIZE AS SHOWN ON PLANS. |
| | |
| | B) WINDOW MULLIONS. |
| | |
| | C) ALL SIMPSON OR USP CONNECTORS SPECIFIED ON PLANS. |
| | PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER PAGE |
| | AND PAGE WHERE CONNECTOR IS SHOWN. |
| | |
| | D) PRECAST LINTELS. |
| | |
| | E) GRACE ICE UNDERLAYMENT.INFORMATION SUBMITTED |
| | NEED TO HAVE THE INSTALLATION SPECIFICATIONS. |
| | COORDINATE INFORMATION WITH ITEM 4 ABOVE. |
| | |
| | F) SINGLE HUNG WINDOWS. PROVIDE INFORMATION THAT |
| | MATCHES INFORMATION GIVEN ON FL #2769.3. IT SHOWS 7/16 |
| | GLAZING. INFORMATION SUBMITTED DOESN'T MATCH. |
| | |
| | |
| | 6- PROVIDE STRUCTURAL WINDOW BUCK DETAILUSING 2X BUCK |
| | TO SHOW COMPLIANCE WITH PRODUCT APPROVAL SUBMITTED FOR |
| | SINGLE HUNG WINDOWS.PRODUCT APPROVAL SUBMITTEDONLY |
| | SHOWS ATTACHMENT TO 2X STRUCTURAL BUCK.SEC. 106.1.2 |
| | CITY AMENDMENTS TO FBC 2004. |
| | |
| | 7- SHEET D1.0: REVISE TYPE OF NAIL TO BE USED IN ROOF |
| | SHEATHING. SEE SEC. R803.2.3.1 OF 2004 FLORIDA |
| | RESIDENTIAL CODE.REQUIRES 8D RING SHANK NAILS. |
| | |
| | 8- OWES $7.26 FOR RADON FEES. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |