| Notes |
| Date |
Text |
| 2007-11-29 14:18:41 | | | | | | | APPLICATION #07110453 | | | ELECTRICAL PLAN REVIEW | | | 214 ALHAMBRA PLACE | | | 11/29/07 | | | WEST PALM BEACH, FL. | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE | | | NOTED. | | | | | | 1} THE FLOOR PLAN (SHEET #4) INDICATES A RECEPTACLE | | | THAT THE PERMANENTLY INSTALLED GENERATOR CONNECTS WITH | | | TO POWER THE EMERGENCY PANEL. SUBMIT DOCUMENTS THAT | | | INDICATE A CORD CONNECTION IS ACCEPTABLE FOR THIS TYPE | | | OF INSTALLATION. THE DIAGRAM SUBMITTED WITH THE | | | MANUFACTURERS PACKAGE INDICATES A HARD WIRED SYSTEM TO | | | A AUTOMATIC TRANSFER SWITCH. CLARIFY THE TRANSFER IS TO | | | BE MANUAL. | | | | | | 2} VERIFY THE GENERATOR SETBACK SHOWN ON THE PLAN | | | COMPLIES WITH THE MANUFACTURERS RECOMMENDED SETBACK. | | | PROVIDE A WRITTEN RESPONSE TO THIS COMMENT. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|