2007-11-29 14:18:41 
  
 APPLICATION #07110453
 ELECTRICAL PLAN REVIEW
 214 ALHAMBRA PLACE
 11/29/07
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE
 NOTED.
  
 1} THE FLOOR PLAN (SHEET #4) INDICATES A RECEPTACLE
 THAT THE PERMANENTLY INSTALLED GENERATOR CONNECTS WITH
 TO POWER THE EMERGENCY PANEL. SUBMIT DOCUMENTS THAT
 INDICATE A CORD CONNECTION IS ACCEPTABLE FOR THIS TYPE
 OF INSTALLATION. THE DIAGRAM SUBMITTED WITH THE
 MANUFACTURERS PACKAGE INDICATES A HARD WIRED SYSTEM TO
 A AUTOMATIC TRANSFER SWITCH. CLARIFY THE TRANSFER IS TO
 BE MANUAL.
  
 2} VERIFY THE GENERATOR SETBACK SHOWN ON THE PLAN
 COMPLIES WITH THE MANUFACTURERS RECOMMENDED SETBACK.
 PROVIDE A WRITTEN RESPONSE TO THIS COMMENT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]