| 2007-11-20 08:45:31 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE |
| | FBC2004 |
| | FACFLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1.PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS, |
| | SIZES, WINDOW TYPE, ROOM DESIGNATIONS.NOTE EXISTING |
| | CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR |
| | BEDROOMS, FBC R310, FBC EB 505.1.SEE FBC R310, FBC EB |
| | 505.1.THE CLEAR OPENING CANNOT BE REDUCED BY MORE |
| | THAN 5%. |
| | |
| | 2.THE WINDOW PRODUCT APPROVAL IS FOR A SINGLE |
| | HUNG/CASEMENT DUAL ACTION WINDOW.PLEASE INDICATE |
| | WHICH PRODUCT YOU WILL BE USING. NOTE THAT THE WINDOW |
| | HAS A 50 3/4" MAX WINDOW HEIGHT, SHEET 1. |
| | |
| | 2.COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR |
| | PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN |
| | ANOTHER FORMAT, FBC*106. |
| | |
| | 3.PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS |
| | WILL BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH |
| | THE INSTALLATION SCHEDULE. |
| | |
| | 4.FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED, |
| | FAC9B72.WWW.FLORIDABUILDING.ORGTHIS IS REQUIRED IN |
| | ADDITION TO THE EVALUATION REPORTS PROVIDED. |
| | |
| | 5.PRODUCT APPROVALS FOR TWO DIFFERENT SHUTTERS WERE |
| | PROVIDED, METAL TECH AND ALL AMERICAN SHUTTERS.IF YOU |
| | ARE USING BOTH, PLEASE INDICATE SHUTTER TYPE FOR EACH |
| | OPENING ON THE FLOOR PLAN OR INSTALLATION SCHEDULE. |
| | |
| | |
| | |
| | |