Plan Review Notes
Plan Review Notes For Permit 07110440
Permit Number 07110440
Review Stop B
Sequence Number 1
Notes
Date Text
2007-11-20 08:45:31****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS,
 SIZES, WINDOW TYPE, ROOM DESIGNATIONS.NOTE EXISTING
 CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR
 BEDROOMS, FBC R310, FBC EB 505.1.SEE FBC R310, FBC EB
 505.1.THE CLEAR OPENING CANNOT BE REDUCED BY MORE
 THAN 5%.
  
 2.THE WINDOW PRODUCT APPROVAL IS FOR A SINGLE
 HUNG/CASEMENT DUAL ACTION WINDOW.PLEASE INDICATE
 WHICH PRODUCT YOU WILL BE USING. NOTE THAT THE WINDOW
 HAS A 50 3/4" MAX WINDOW HEIGHT, SHEET 1.
  
 2.COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR
 PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT, FBC*106.
  
 3.PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS
 WILL BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH
 THE INSTALLATION SCHEDULE.
  
 4.FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9B72.WWW.FLORIDABUILDING.ORGTHIS IS REQUIRED IN
 ADDITION TO THE EVALUATION REPORTS PROVIDED.
  
 5.PRODUCT APPROVALS FOR TWO DIFFERENT SHUTTERS WERE
 PROVIDED, METAL TECH AND ALL AMERICAN SHUTTERS.IF YOU
 ARE USING BOTH, PLEASE INDICATE SHUTTER TYPE FOR EACH
 OPENING ON THE FLOOR PLAN OR INSTALLATION SCHEDULE.
  
  
  
  