| 2008-07-23 10:41:59 | ***AT CONTRACTOR'S RISK*** |
| | |
| | ****PROVISO**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| | FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | ENGINEER TO ADDRESS PRIOR TO C.O., SUBMIT AS REVISION: |
| | |
| | |
| | 1.)FBC1004, DECLARE OCCUPANCY CLASSIFICATION FOR EACH |
| | PORTION OF BUILDING. SEE PREVIOUS LIST, ITEM 7. DECLARE |
| | OCCUPANT LOAD, FBC1004.1. |
| | |
| | S2 DECLARED.PLEASE SEE FBC311.2, CLOTHING IS INCLUDED |
| | IN MODERATE-HAZARD STORAGE, S1.OFFICE SHOULD BE |
| | BUSINESS USE, FBC304.SEE FBC302; THIS APPEARS TO BE |
| | TOO LARGE TO BE ACCESSORY USE, AND INCIDENTAL USE IS TO |
| | BE SEPARATED.IT IS POSSIBLE THAT THE BUILDING |
| | COMPLIES WITH A NON SEPARATED USE FBC302.3.1 BUT |
| | NOTHING ON THE PLAN SHOWS COMPLIANCE. |
| | |
| | SUBMIT AS A REVISION, PRIOR TO INSTALLATION: |
| | |
| | 2.)PROVIDE PRODUCT APPROVALS FOR THE MULLIONS, |
| | FAC9B72, WWW.FLORIDABUILDING.ORG. PRODUCT APPROVALS ARE |
| | TO BE APPROVED BY DESIGNER OF RECORD (SHOP DRAWING |
| | REVIEW STAMP OR LETTER), FBC*106.3.3. |
| | |
| | 3.)SHEET 3 SPECIFIES DESIGN PRESSURES OF +35/-38.2. |
| | SHEET 1 COMPONENTS & CLADDING WIND PRESSURES IS +-54.6. |
| | SEE THE FIXED WINDOW PRODUCT APPROVAL.NOT ALL SIZES |
| | MEET THE PRESSURE +-54.6.WINDOW WIDTHS WERE NOT |
| | PROVIDED.PLEASE CLARIFY DESIGN PRESSURES AND PROVIDE |
| | ENOUGH INFORMATION TO DETERMINE CODE COMPLIANCE. SUBMIT |
| | AS A REVISION WITH PRODUCT APPROVALS REVIEWED BY |
| | ENGINEER. |