2008-07-23 10:41:59***AT CONTRACTOR'S RISK***
  
 ****PROVISO****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 ENGINEER TO ADDRESS PRIOR TO C.O., SUBMIT AS REVISION:
  
  
 1.)FBC1004, DECLARE OCCUPANCY CLASSIFICATION FOR EACH
 PORTION OF BUILDING. SEE PREVIOUS LIST, ITEM 7. DECLARE
 OCCUPANT LOAD, FBC1004.1.
  
 S2 DECLARED.PLEASE SEE FBC311.2, CLOTHING IS INCLUDED
 IN MODERATE-HAZARD STORAGE, S1.OFFICE SHOULD BE
 BUSINESS USE, FBC304.SEE FBC302; THIS APPEARS TO BE
 TOO LARGE TO BE ACCESSORY USE, AND INCIDENTAL USE IS TO
 BE SEPARATED.IT IS POSSIBLE THAT THE BUILDING
 COMPLIES WITH A NON SEPARATED USE FBC302.3.1 BUT
 NOTHING ON THE PLAN SHOWS COMPLIANCE.
  
 SUBMIT AS A REVISION, PRIOR TO INSTALLATION:
  
 2.)PROVIDE PRODUCT APPROVALS FOR THE MULLIONS,
 FAC9B72, WWW.FLORIDABUILDING.ORG. PRODUCT APPROVALS ARE
 TO BE APPROVED BY DESIGNER OF RECORD (SHOP DRAWING
 REVIEW STAMP OR LETTER), FBC*106.3.3.
  
 3.)SHEET 3 SPECIFIES DESIGN PRESSURES OF +35/-38.2.
 SHEET 1 COMPONENTS & CLADDING WIND PRESSURES IS +-54.6.
 SEE THE FIXED WINDOW PRODUCT APPROVAL.NOT ALL SIZES
 MEET THE PRESSURE +-54.6.WINDOW WIDTHS WERE NOT
 PROVIDED.PLEASE CLARIFY DESIGN PRESSURES AND PROVIDE
 ENOUGH INFORMATION TO DETERMINE CODE COMPLIANCE. SUBMIT
 AS A REVISION WITH PRODUCT APPROVALS REVIEWED BY
 ENGINEER.