| 2008-07-21 13:59:47 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | 1-2.)ADDRESSED. |
| | |
| | 3.)FBC1004, DECLARE OCCUPANCY CLASSIFICATION FOR EACH |
| | PORTION OF BUILDING. SEE PREVIOUS LIST, ITEM 7. DECLARE |
| | OCCUPANT LOAD, FBC1004.1. |
| | |
| | S2 DECLARED.PLEASE SEE FBC311.2, CLOTHING IS INCLUDED |
| | IN MODERATE-HAZARD STORAGE, S1.OFFICE SHOULD BE |
| | BUSINESS USE, FBC304.SEE FBC302; THIS APPEARS TO BE |
| | TOO LARGE TO BE ACCESSORY USE, AND INCIDENTAL USE IS TO |
| | BE SEPARATED.IT IS POSSIBLE THAT THE BUILDING |
| | COMPLIES WITH A NON SEPARATED USE FBC302.3.1 BUT |
| | NOTHING ON THE PLAN SHOWS COMPLIANCE. |
| | |
| | 4.-7.)ADDRESSED. |
| | |
| | 8.)SEE PREVIOUS COMMENT LIST, ITEM 6.PROVIDE CONDO |
| | ASSOCIATION APPROVAL AS YOU ARE ALTERING THE OUTSIDE OF |
| | THE BUILDING. |
| | |
| | FOURTH REQUEST.PLEASE DO NOT RESUBMIT WITHOUT THE |
| | LETTER. |
| | |
| | 9.)PROVIDE PRODUCT APPROVALS FOR THE MULLIONS, |
| | FAC9B72, WWW.FLORIDABUILDING.ORG. PRODUCT APPROVALS ARE |
| | TO BE APPROVED BY DESIGNER OF RECORD (SHOP DRAWING |
| | REVIEW STAMP OR LETTER), FBC*106.3.3. |
| | |
| | 10-19.)ADDRESSED. |
| | |
| | 20.)PLEASE PROVIDE A BREAKDOWN OF COST FOR THIS |
| | PERMIT. |
| | |
| | PROVIDE A REASONABLE VALUE FOR THIS JOB.OTHERWISE AN |
| | ESTIMATED VALUE WILL BE PROVIDED USING MARSHALL & SWIFT |
| | OR MEANS. |
| | |
| | 21.)WHEN RESUBMITTING, PROVIDE A RESPONSE LETTER |
| | EXPLAINING HOW EACH ITEM WAS ADDRESSED. |
| | |
| | 22-24)ADDRESSED. |
| | |
| | NEW COMMENTS: |
| | |
| | 25.)SHEET 3 SPECIFIES DESIGN PRESSURES OF +35/-38.2. |
| | SHEET 1 COMPONENTS & CLADDING WIND PRESSURES IS +-54.6. |
| | SEE THE FIXED WINDOW PRODUCT APPROVAL.NOT ALL SIZES |
| | MEET THE PRESSURE +-54.6.WINDOW WIDTHS WERE NOT |
| | PROVIDED.PLEASE CLARIFY DESIGN PRESSURES AND PROVIDE |
| | ENOUGH INFORMATION TO DETERMINE CODE COMPLIANCE. |
| | |