| 2008-04-25 14:46:36 | ****CORRECTIONS**** |
| | ****COMMENTS FROM PREVIOUS LIST, SAME PLANS SUBMITTED |
| | DATED 1/11/8*** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| | FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | |
| | 1.)INCLUDE A CODE SUMMARY; BUILDING TYPE FBC6, |
| | BUILDING HEIGHT AND AREA FBC5, SPRINKLER INFORMATION, |
| | OCCUPANCY CLASSIFICATION FBC 3 AND AREA PER OCCUPANCY. |
| | |
| | 2.)SEE PREVIOUS LIST, ITEM 7.THIS APPEARS TO BE A |
| | CHANGE OF OCCUPANCY AS YOU MAKE REFERENCE TO "NEW |
| | OFFICE".PLEASE MAKE NOTE CHANGE OF OCCUPANCY IN THE |
| | CODE SUMMARY. |
| | |
| | 3.)FBC1004, DECLARE OCCUPANCY CLASSIFICATION FOR EACH |
| | PORTION OF BUILDING. SEE PREVIOUS LIST, ITEM 7. DECLARE |
| | OCCUPANT LOAD, FBC1004.1. |
| | |
| | 4.)DECLARE HAZARD CATEGORY FOR LIFE SAFETY AND EXITS, |
| | HEIGHTS AND AREAS, AND EXPOSURE OF EXTERIOR WALLS FBC |
| | TABLES 812.4.1, 812.4.2, AND 812.4.3 RESPECTIVELY. |
| | DECLARE EXISTING AND PROPOSED. |
| | |
| | 5.)CLARIFY WHETHER THE UPSTAIRS OFFICE IS A MEZZANINE |
| | OR SECOND STORY.IF THIS IS A MEZZANINE, SHOW |
| | COMPLIANCE WITH FBC505.2, FBC505.4.PROVIDE |
| | CALCULATIONS AS THE ORIGINAL CONSTRUCTION WAS BUILT |
| | BASED ON UNENCLOSED MEZZANINE SPACE. |
| | |
| | 6.)SEE PREVIOUS COMMENT LIST, ITEM 3.GOVERNING CODE |
| | SHOULD INCLUDE 2007 REVISIONS WHICH BECAME EFFECTIVE |
| | JULY 1, 2007.PLEASE REVISE. |
| | |
| | 7.)SEE PREVIOUS COMMENT LIST, ITEM 4.PROVIDE A |
| | FRAMING DETAIL FOR THE NEW WALL OPENING. |
| | |
| | 8.)SEE PREVIOUS COMMENT LIST, ITEM 6.PROVIDE CONDO |
| | ASSOCIATION APPROVAL AS YOU ARE ALTERING THE OUTSIDE OF |
| | THE BUILDING. |
| | |
| | THE LETTER PROVIDED FOR ZONING STATES THAT THE CONDO |
| | ASSOCIATION DOES NOT REQUIRE APPROVAL FOR INTERIOR |
| | ALTERATION.THIS JOB INCLUDES INSTALLING WINDOWS WHICH |
| | IS ON THE OUTSIDE OF THE BUILDING.THE AHJ REQUIRES A |
| | LETTER FROM THE CONDO ASSOCIATION AS TECHNICALLY THE |
| | OWNER DOES NOT OWN THE OUTSIDE OF THE BUILDING. |
| | |
| | 9.)PROVIDE PRODUCT APPROVALS FOR THE PROPOSED WINDOWS |
| | AND MULLIONS, FAC9B72, WWW.FLORIDABUILDING.ORG. PRODUCT |
| | APPROVALS ARE TO BE APPROVED BY DESIGNER OF RECORD |
| | (SHOP DRAWING REVIEW STAMP OR LETTER), FBC*106.3.3. |
| | |
| | 10.)ADDRESSED. |
| | |
| | 11.)PROVIDE DETAIL MARKERS ON THE PLAN AND LABEL THE |
| | DETAIL.NOTE THAT THE GRAPHIC FOR THE L SHAPE WALL AT |
| | THE DISPLAY/STORAGE AREA IS APPROXIMATELY FOUR TIMES |
| | THE WIDTH FOR THE DRESSING ROOM PARTITION WALLS. ONLY |
| | ONE WALL DETAIL WAS PROVIDED.IF YOU ARE USING THE |
| | SAME DETAIL FOR BOTH WALLS, PLEASE EXPLAIN WHY ONE IS |
| | SO MUCH WIDER THAN THE OTHER ON THE FLOOR PLAN. |
| | |
| | 12.)THE L SHAPE ON THE PLAN APPEARS TO BE A WALL.IF |
| | IT IS A WALL, CLARIFY HOW THIS WILL BE A DISPLAY AREA |
| | AS IT IS NOT VISIBLE. |
| | |
| | 13.)THE TWO APPLICATIONS SUBMITTED WERE FOR A |
| | DRESSING ROOM AREA.THE LETTER SIGNED BY JAE KIM |
| | STATES THAT THIS IS A WAREHOUSE, NO ACCESS TO THE |
| | PUBLIC, AND THE DRESSING ROOM IS TO BE USED BY MODELS |
| | ONLY.THE PLANS SHOW THIS AS STORAGE/DISPLAY, NOT |
| | DRESSING ROOM FOR MODELS ONLY (NOT PUBLIC).THE |
| | ENGINEER IS TO INCORPORATE A SPECIFIC DESCRIPTION OF |
| | USE OF THIS AREA INTO THE SIGNED AND SEALED PLAN, ALSO |
| | SUBMIT A SIGNED AND SEALED LETTER IF NECESSARY FOR |
| | CLARIFICATION, AS THE PLAN CURRENTLY CONFLICTS WITH THE |
| | LETTER AND APPLICATION.WITHOUT SPECIFIC INFORMATION |
| | REGARDING THE USE, OCCUPANCY, AND OCCUPANT LOAD OF THIS |
| | AREA, CODE REQUIREMENTS CANNOT BE DETERMINED. |
| | |
| | 14.)FIRE SPRINKLER PLANS REQUIRED AT THIS TIME (HEAD |
| | SCHEMATIC) IF SPRINKLERS ARE REQUIRED FOR CODE |
| | COMPLIANCE, FBC*106.3.5.1.1(5), FS553.79 (2). |
| | |
| | 15.)VERTICAL ACCESSIBILITY REQUIRED FOR THE OFFICE |
| | AREA.SEE FBC11-4.1.6(1)(K)(III).IF VERTICAL |
| | ACCESSIBILITY IS NOT BEING PROVIDED, ANY APPLICABLE |
| | EXEMPTIONS ARE TO BE INCORPORATED INTO THE PLAN. |
| | |
| | 16.)SHOW RACK DISTANCE.FBC1016.3. |
| | |
| | 17.)SIGNATURE FOR ENGINEER TO BE AN ORIGINAL PER |
| | FBPE, FS471. |
| | |
| | 18.)CERTIFICATE OF AUTHORIZATION TO BE INCLUDED ON |
| | EACH SHEETS, FAC61G15-23.002. |
| | |
| | 19.)CODE COMPLIANCE AND A COMPLETE CHECKLIST CANNOT |
| | BE PROVIDED AT THIS TIME DUE TO INSUFFICIENT OR |
| | INCONSISTENT INFORMATION. |
| | |
| | 20.)PLEASE PROVIDE A BREAKDOWN OF COST FOR THIS |
| | PERMIT. |
| | |
| | NEW COMMENTS: |
| | |
| | 21.)WHEN RESUBMITTING, PROVIDE A RESPONSE LETTER |
| | EXPLAINING HOW EACH ITEM WAS ADDRESSED. |
| | |
| | 22.)SEE ATTACHED FS553.80(2)(B).A 4X PLAN REVIEW |
| | FEE WILL BE CHARGED IF THE COMMENTS ARE NOT PROPERLY |
| | ADDRESSED A THIRD TIME. |
| | |
| | 23.)SEE COMMENT 9.AS PRODUCT APPROVALS HAVE NOT |
| | BEEN SUBMITTED, IT IS NOT CLEAR IF THE ENGINEER'S |
| | INTENTION IS FOR THE OVERHEAD GARAGE DOOR IS TO BE USED |
| | AS IMPACT PROTECTION.PLEASE CLARIFY THIS ISSUE. |
| | |
| | 24.)TWO SETS OF PLANS REQUIRED FOR PERMIT ISSUANCE. |
| | ONE SET WAS RETAINED FROM PREVIOUS REVIEW AND WILL NOT |
| | BE RETURNED TO THE CONTRACTOR, BUT REGARDLESS CANNOT BE |
| | USED FOR PERMITTING AS IT IS NOT CODE COMPLIANT AND THE |
| | SIGNATURE IS A PHOTOCOPY.PLANS NEED TO BE REVISED |
| | ADDRESSING ALL COMMENTS FOR ALL TRADES AND TWO SETS |
| | WITH ORIGINAL SIGNATURES SUBMITTED.TWO SETS OF ALL |
| | PERMIT DOCUMENTS WILL BE REQUIRED (INCLUDING ANY |
| | APPLICABLE LETTERS, PRODUCT APPROVALS, ETC.). |
| | |