Plan Review Notes
Plan Review Notes For Permit 07110439
Permit Number 07110439
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2008-02-28 16:38:12*****DENIED*****
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
 1.WORKING PLANS SHALL BE DRAWN TO AN INDICATED SCALE,
 ON SHEET(S) OF UNIFORM SIZE, WITH A PLAN OF THE/EACH
 FLOOR, AND SHALL SHOW THOSE ITEMS THAT PERTAIN TO THE
 SCOPE OF WORK WHICH INCLUDES: * POINT OF COMPASS*
 PLEASE SHOW POINT OF COMPASS
  
 2.PROVIDE OCCUPANCY CLASSIFICATION.ADDRESS
 COMMENT
  
 3.DOES THE BUILDINGHAVE A FIRE ALARM SYSTEM OR
 DEVICES?IF SO, SEPARATE PLANS AND PERMIT WILL BE
 REQUIRED IF THE SYSTEM IS TO BE ALTERED DUE TO THE
 SCOPE OF WORK.ADDRESS COMMENT
  
 4.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD
 COMMENT TO AN APPROPIATE PLAN SHEET
  
 5.COMBUSTIBLE WASTE MATERIAL, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.ADD
 COMMENT TO AN APPROPIATE PLAN SHEET
  
 6.DURING THE SCOPE OF WORK, ALL REQUIRED EXIT
 COMPONENTS, FIRE-RESISTIVE ASSEMBLIES AND CONSTRUCTION
 SHALL BE MAINTAINED.ADD COMMENT TO AN APPROPIATE
 PLAN SHEET
  
 7.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.ADD NFPA 101 - 2003 EDITION - TO PLAN
 SHEET 1 OF 4 IN THE NOTE REFERENCING CONSTRUCTION
  
 8.SPECIFY THE INTERIOR FINISH MATERIAL FOR THE NEW
 PARTITION WALLS AND NEW OFFICE IN TERMS OF CLASS A,
 CLASS B, OR CLASS C.ADDRESS COMMENT
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722