| 2008-02-28 16:38:12 | *****DENIED***** |
| | |
| | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE |
| | PLAN REVIEW STILL NEED TO BE ADDRESSED: |
| | |
| | 1.WORKING PLANS SHALL BE DRAWN TO AN INDICATED SCALE, |
| | ON SHEET(S) OF UNIFORM SIZE, WITH A PLAN OF THE/EACH |
| | FLOOR, AND SHALL SHOW THOSE ITEMS THAT PERTAIN TO THE |
| | SCOPE OF WORK WHICH INCLUDES: * POINT OF COMPASS* |
| | PLEASE SHOW POINT OF COMPASS |
| | |
| | 2.PROVIDE OCCUPANCY CLASSIFICATION.ADDRESS |
| | COMMENT |
| | |
| | 3.DOES THE BUILDINGHAVE A FIRE ALARM SYSTEM OR |
| | DEVICES?IF SO, SEPARATE PLANS AND PERMIT WILL BE |
| | REQUIRED IF THE SYSTEM IS TO BE ALTERED DUE TO THE |
| | SCOPE OF WORK.ADDRESS COMMENT |
| | |
| | 4.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD |
| | COMMENT TO AN APPROPIATE PLAN SHEET |
| | |
| | 5.COMBUSTIBLE WASTE MATERIAL, DUST, AND DEBRIS SHALL |
| | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR |
| | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.ADD |
| | COMMENT TO AN APPROPIATE PLAN SHEET |
| | |
| | 6.DURING THE SCOPE OF WORK, ALL REQUIRED EXIT |
| | COMPONENTS, FIRE-RESISTIVE ASSEMBLIES AND CONSTRUCTION |
| | SHALL BE MAINTAINED.ADD COMMENT TO AN APPROPIATE |
| | PLAN SHEET |
| | |
| | 7.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE |
| | REFERENCED.ADD NFPA 101 - 2003 EDITION - TO PLAN |
| | SHEET 1 OF 4 IN THE NOTE REFERENCING CONSTRUCTION |
| | |
| | 8.SPECIFY THE INTERIOR FINISH MATERIAL FOR THE NEW |
| | PARTITION WALLS AND NEW OFFICE IN TERMS OF CLASS A, |
| | CLASS B, OR CLASS C.ADDRESS COMMENT |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |