| Plan Review Notes For Permit 07110439 |
| Permit Number |
07110439 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-03-24 12:19:00 | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | THIS COMMENT WAS NOT RESPONDED TO. | | | | | | 4} INDICATE COMPLIANCE WITH 13-415.2ABC.1 OR 13-415.2B | | | OR 13-415.2.C.1 LIGHTING DENSITIES.THIS MAY BE SHOWN ON | | | THE PLAN BY LISTING THE FIXTURE TYPES AND WATTAGE PER | | | 13-415.2ABC.1.2 AND USING THE TABLES MENTIONED IN THIS | | | COMMENT. THIS COMMENT IS BROUGHT FOR THE NEW TRACK | | | LIGHTING BEING INSTALLED THE FIRST FLOOR. | | | | | | THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK SHALL | | | INDICATE THE CERTIFICATE OF AUTHORIZATIONNUMBER ALONG | | | WITH OTHER INFORMATION REQUIRED BY 61G15-23.002 FLORIDA | | | ADMINISTRATIVE CODE. | | | | | | TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR REVIEW | | | PER 106.1 FBC AS AMENDED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|