Date Text
2008-03-24 12:19:00 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 THIS COMMENT WAS NOT RESPONDED TO.
  
 4} INDICATE COMPLIANCE WITH 13-415.2ABC.1 OR 13-415.2B
 OR 13-415.2.C.1 LIGHTING DENSITIES.THIS MAY BE SHOWN ON
 THE PLAN BY LISTING THE FIXTURE TYPES AND WATTAGE PER
 13-415.2ABC.1.2 AND USING THE TABLES MENTIONED IN THIS
 COMMENT. THIS COMMENT IS BROUGHT FOR THE NEW TRACK
 LIGHTING BEING INSTALLED THE FIRST FLOOR.
  
 THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK SHALL
 INDICATE THE CERTIFICATE OF AUTHORIZATIONNUMBER ALONG
 WITH OTHER INFORMATION REQUIRED BY 61G15-23.002 FLORIDA
 ADMINISTRATIVE CODE.
  
 TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR REVIEW
 PER 106.1 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718