2007-12-04 09:22:11*****DENIED*****
  
 1.WORKING PLANS SHALL BE DRAWN TO AN INDICATED SCALE,
 ON SHEET(S) OF UNIFORM SIZE, WITH A PLAN OF THE/EACH
 FLOOR, AND SHALL SHOW THOSE ITEMS THAT PERTAIN TO THE
 SCOPE OF WORK WHICH INCLUDES: * NAME OF OWNER AND
 OCCUPANT, * LOCATION, INCLUDING STREET ADDRESS, * POINT
 OF COMPASS, * LOCATION OF PARTITIONS AND FIRE WALLS.
  
 2.PROVIDE OCCUPANCY CLASSIFICATION.
  
 3.IS THE BUILDING FIRE SPRINKLERED AND/OR HAS A FIRE
 ALARM SYSTEM OR DEVICES?IF SO, SEPARATE PLANS AND
 PERMIT WILL BE REQUIRED IF THE SYSTEM(S) HAS TO BE
 ALTERED DUE TO THE SCOPE OF WORK.
  
 4.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 5.COMBUSTIBLE WASTE MATERIAL, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 6.DURING THE SCOPE OF WORK, ALL REQUIRED EXIT
 COMPONENTS, FIRE-RESISTIVE ASSEMBLIES AND CONSTRUCTION
 SHALL BE MAINTAINED.
  
 7.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 8.SPECIFY THE INTERIOR FINISH MATERIAL FOR THE NEW
 PARTITION WALLS IN TERMS OF CLASS A, CLASS B, OR CLASS
 C.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED
  
  