| Plan Review Notes For Permit 07110439 |
| Permit Number |
07110439 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-03-04 16:05:07 | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} THE LOAD CALCULATION SUBMITTED IS INCOMPLETE, SEE | | | ARTICLE 220, 2005 NEC. RECEPTACLE LOAD NOT SHOWN, | | | LIGHTS NOT CALCULATED (SEE CONTINUOUS LOADS | | | 210.2(A).AND THE TERM "MISC"NEEDS TO BE MORE | | | SPECIFIC. | | | | | | 2} THE OCP FOR THE "NEW " AHU #2 IS INCORRECT FOR A | | | 10000 WATT UNIT. SEE 424.3(B), 2005 NEC. | | | | | | 3} INDICATE COMPLIANCE WITH 7.8 NFPA-101 FOR EGRESS | | | REQUIREMENTS AT THE STAIRS. | | | | | | 4} INDICATE COMPLIANCE WITH 13-415.2ABC.1 OR 13-415.2B | | | OR 13-415.2.C.1 LIGHTING DENSITIES.THIS MAY BE SHOWN ON | | | THE PLAN BY LISTING THE FIXTURE TYPES AND WATTAGE PER | | | 13-415.2ABC.1.2 AND USING THE TABLES MENTIONED IN THIS | | | COMMENT. THIS COMMENT IS BROUGHT FOR THE NEW TRACK | | | LIGHTING BEING INSTALLED THE FIRST FLOOR. | | | | | | 5} THE ARCHITECT?S SIGNATURE IS A PHOTOCOPY. WHEN | | | SUBMITTING FOR PERMITTING THE SIGNATURE MUST BE WET PER | | | 481.221(1)(A) FLORIDA STATUTES. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|