Plan Review Notes
Plan Review Notes For Permit 07110439
Permit Number 07110439
Review Stop E
Sequence Number 1
Notes
Date Text
2008-03-04 16:05:07 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE LOAD CALCULATION SUBMITTED IS INCOMPLETE, SEE
 ARTICLE 220, 2005 NEC. RECEPTACLE LOAD NOT SHOWN,
 LIGHTS NOT CALCULATED (SEE CONTINUOUS LOADS
 210.2(A).AND THE TERM "MISC"NEEDS TO BE MORE
 SPECIFIC.
  
 2} THE OCP FOR THE "NEW " AHU #2 IS INCORRECT FOR A
 10000 WATT UNIT. SEE 424.3(B), 2005 NEC.
  
 3} INDICATE COMPLIANCE WITH 7.8 NFPA-101 FOR EGRESS
 REQUIREMENTS AT THE STAIRS.
  
 4} INDICATE COMPLIANCE WITH 13-415.2ABC.1 OR 13-415.2B
 OR 13-415.2.C.1 LIGHTING DENSITIES.THIS MAY BE SHOWN ON
 THE PLAN BY LISTING THE FIXTURE TYPES AND WATTAGE PER
 13-415.2ABC.1.2 AND USING THE TABLES MENTIONED IN THIS
 COMMENT. THIS COMMENT IS BROUGHT FOR THE NEW TRACK
 LIGHTING BEING INSTALLED THE FIRST FLOOR.
  
 5} THE ARCHITECT?S SIGNATURE IS A PHOTOCOPY. WHEN
 SUBMITTING FOR PERMITTING THE SIGNATURE MUST BE WET PER
 481.221(1)(A) FLORIDA STATUTES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718