| 2007-12-11 07:16:34 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. NOTE: A MINIMUM OF TWO SETS OF DRAWINGS SHALL BE |
| | SUBMITTED WITH THE FOLLOWING INFORMATION. PER *106.1.1, |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | A} DEMO FLOOR PLAN: CLEARLY INDICATING THE DEMO OF ALL |
| | WALLS AND PLUMBING SYSTEMS. PER FBC-2004 PLUMBING, |
| | SECTION *704.5 DEAD ENDS: IN THE INSTALLATION OR |
| | REMOVAL OF ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS |
| | SHALL BE PROHIBITED. A DEMO PLUMBING PERMIT REQUIRED |
| | AND INSPECTION REQUIRED OF DEMO WORK PRIOR TO COVERING |
| | DEMO WORK WITH FINNISH WALLS, CIELINGS, OR POURED |
| | CONCRETE SLABS. |
| | |
| | B} NEW FLOOR PLAN: CLEARLY INDICATE THE PROPOSED NEW |
| | LAYOUT OF THE SPACE. |
| | |
| | 2. BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH |
| | SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE |
| | MEDIUM. PER *106.1.3, QUALITY OF BUILDING PLANS. |
| | |
| | 3. FBC-2004 CHAPTER 1,SECTION *106.3.4.3: |
| | THE RESUBMITTED DRAWINGS SHALL HAVE THE PERSON |
| | RESPONSIBLE FOR THE DESIGN OF THE DRAWING SHALL CLEARLY |
| | PRINT AND SIGN NAME, AND ALSO DATE DRAWING. IF THE |
| | DESIGN PROFESSIONAL IS AN ARCHITECT OR ENGINEER, THEN |
| | HE OR SHE SHALL AFIX HIS OR HER OFFICIAL SEAL, |
| | SIGNATURE AND DATE TO SAID DRAWINGS. PER FLORIDA |
| | STATUTES *481 AND *471. PLEASE DO THIS PRIOR TO |
| | RESUBMITTING. |
| | |
| | 4. PER FS 713.13 (1) THRU (6): A NOTICE OF |
| | COMMENCEMENT IS REQUIRED FROM THE - PALM BEACH COUNTY |
| | COURTHOUSE - 4TH FLOOR RECORDING DEPT. 205 N. DIXIE |
| | HWY., BEFORE A PERMIT CAN BE ISSUED. PER FS 713.13 (2): |
| | IF THE IMPROVEMENT DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| | AFTER THE RECORDING THEREOF, SUCH NOTICE IS VOID AND OF |
| | NO FURTHER EFFECT. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |