| 2008-03-24 16:37:04 | REVISED THREE PRODUCT APPROVALS | | | | | | DENIED BY BUILDING | | | | | | 1) THE PRODUCT APPROVALS FOR THE SH-4000 PGT WINDOWS | | | AND THE MASONITE STEEL DOORS HAVE BEEN REVIEWED FOR | | | CODE COMPLIANCE. | | | | | | 2) THE INSTALLATION SCHEDULE FOR THE ALUFAB STORM | | | PANELS IS INCORRECT. THE MOUNT TYPE SPECIFIED IS FOR | | | VERTICAL INSTALLATION. THE EDGE DISTANCE IS SPECIFIED | | | AS 2" WHICH REQUIRES THE ANCHOR SPACING TO BE REDUCED | | | BY HALF. PLEASE CORRECT. | | | | | | 3) THE NUMBER OF PRODUCT APPROVALS REVISED IS THREE. | | | THEREFORE AND ADDITIONAL $20.00 IN REVISION FEES IS | | | DUE. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|