| Plan Review Notes For Permit 07110417 |
| Permit Number |
07110417 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-01-18 09:14:33 | DENIED; | | | 1. ALL INFORMATION/DRAWINGS/SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE | | | NAME AND SIGNATURE OF THE PERSON RESPON- | | | SIBLE FOR THE DESIGN. SECTION 104.2.1 | | | 2. AUTOMATIC CLOTHS WASHER FIXTURE DRAIN | | | SHALL CONNECT TO A BRANCH DRAIN A MINIMUM | | | OF 3" IN DIAMETER. SEE FBC-PLUMBING SECTION 406.3. | | | 3. W/M NOT VENTED. SEE FBC RESIDENTIAL SECTION | | | P3101.2.1 | | | 4. CLEANOUT REQUIRED ON WASHER STACK, SECTION | | | P3005.2.6 | | | 5. W/M DISCHARGE CANNOT DRAIN INTO A BATHROOM | | | GROUP. MUST BE DOWN STREAM. SECTION | | | P3108.1. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 | | | |
|