| 2007-11-28 12:26:40 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) THE MECHANICAL PLAN NEEDS TO SHOW THE SIZE OF THE |
| | RETURN AIR TRANSFER DUCTS (FLEX) TO THE BEDROOMS, SEE |
| | 2004 FBC/R M1602.4. |
| | |
| | 2) SHOW ON MECHANICAL PLAN HOW THE AIR IS RETURNING |
| | BACK TO THE AIR HANDLER, SEE 2004 FBC/R M1602.1. |
| | |
| | 3) MECHANICAL PLANS SHOWS THE AIR HANDLES SUPPLYING |
| | 1,032 CFM'S TO THE HOUSE, WHEN THE UNIT ONLY SUPPLIES |
| | 800 CFM'S. PLEASE SUBMIT MANUAL D CALCULATIONS FOR |
| | RESIDENTIAL DUCT DESIGN, PER 2004 FBC/R M1601.1 AND FBC |
| | 13-610.1.ABC.1. DUCT SYSTEMS SERVING HEATING, COOLING |
| | AND VENTILATION EQUIPMENT SHALL BE FABRICATED IN |
| | ACCORDANCE WITH THE PROVISIONS OF THIS SECTION AND ACCA |
| | MANUAL D OR OTHER APPROVED METHODS. (AND)ALL AIR |
| | DISTRIBUTION SYSTEMS SHALL BE SIZED AND DESIGNED IN |
| | ACCORDANCE WITH RECOGNIZED ENGINEERING STANDARDS SUCH |
| | AS ACCA MANUAL D OR OTHER STANDARDS BASED ON THE |
| | FOLLOWING: |
| | |
| | 4) ADD THE A/C EQUIPMENT LISTING WITH ALL PERTINENT |
| | INFORMATION TO THE MECHANICAL PLAN NOT A SEPARATE |
| | PAPER, SEE 2004 WPB AMEND. 106.3.5.4 (10). |
| | |
| | 5) SHOW THE LOCATION OF THE A/C CONDENSER UNIT ON THE |
| | MECHANICAL PLAN. |
| | |
| | MECHANICAL PLAN REVIEW BY; |