Text |
| 2007-11-19 14:28:07 | 2004 FBC W/2007 REVISIONS | | | RESIDENTIAL REHAB | | | | | | DENIED BY BUILDING | | | | | | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT | | | MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) THE SCOPE OF WORK ON A1 SPECIFIES THAT A 2'-8" STEEL | | | DOOR IS TO BE INSTALLED. THE PLANS SHOW A 2'-8" INSWING | | | EXTERIOR DOOR AND THE PRODUCT APPROVAL THAT WAS | | | SUBMITTED IS FOR AN OUTSWING DOOR. PLEASE CLARIFY.FBC | | | *106.1.1 CITY AMENDMENTS | | | | | | 3)SPECIFY THE COMPONENT AND CLADDING PRESSURES FOR | | | THE EXTERIOR DOOR THAT IS BEING REPLACED. SEE FBC TABLE | | | R301.2(2). | | | | | | 4) SUBMIT A KEY PLAN AND INSTALLATION SCHEDULE FOR THE | | | STORM PANELS. SPECIFY THE MOUNT TYPE, ANCHOR TYPE AND | | | SPACING, SPAN, EDGE DISTANCE, ETC. THIS INFORMATION IS | | | CONTAINED IN THE PRODUCT APPROVAL. SEE ATTACHED SAMPLE | | | INSTALLATION SCHEDULE. | | | | | | 5) SUBMIT ENERGY CALCULATIONS ON FORM 600C-04R AS | | | REQUIRED BY FBC 13-101.4.1. | | | | | | - ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|