| 2008-05-03 06:40:55 | BUILDING PLAN REVIEW |
| | PERMIT: 07110407 |
| | ADD: 1411 N. FLAGLER DR 8900B |
| | CONT: ANDERSON MOORE CONST. |
| | TEL: (561)753-7400 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 5-3-08 |
| | REVIEW: #2 REVISION |
| | ACTION: DENIED |
| | |
| | 1)THE ORIGINAL PLANS SHOWS WALL P-3 BEHIND THE |
| | ELECTRICAL PANELS ON SHEET A.1. THE REVISION NOW SHOWS |
| | THE SAME WALL IN FRONT OF THE ELECTRICAL PANELS WHICH |
| | WILL MAKE THE PANELS INACCESSIBLE. IT SEEMS AS THOUGH A |
| | NEW ELECTRICAL CLOSET IS BEING CREATED BY ADDING THESE |
| | DOORS WHICH MAY BE AN ELECTRICAL VIOLATION. THE |
| | ELECTRICAL PAGES SHALL BE REVISED TO SHOW THE LOCATION |
| | OF THE DOORS IN RELATION TO THE PANELS FOR THE REQUIRED |
| | CLEARANCE FOR ELECTRICAL CLOSETS. THE ONLY CODE SECTION |
| | IN THE BUILDING CODE WHICH COVERS THIS SITUATION IS FBC |
| | 2701.1 SCOPE. |
| | THIS CHAPTER GOVERNS THE ELECTRICAL COMPONENTS, |
| | EQUIPMENT AND SYSTEMS USED IN BUILDINGS AND STRUCTURES |
| | COVERED BY THIS CODE. ELECTRICAL COMPONENTS, EQUIPMENT |
| | AND SYSTEMS SHALL BE DESIGNED AND CONSTRUCTED IN |
| | ACCORDANCE WITH THE PROVISIONS OF THE NFPA 70, NATIONAL |
| | ELECTRICAL CODE, EXCEPT ARTICLE 80. |
| | THE ELECTRICAL PLAN REVIEWER WILL HAVE TO REVIEW THIS |
| | CHANGE BEFORE THE DOORS ARE APPROVED. ADDITIONAL |
| | INFORMATION IS REQUIRED WPB AMENDMENTS 106.1.2 |
| | |
| | **SAME PLANS SUBMITTED WITH SHET E.1 NEEDS ELECTRIC |
| | APPROVAL** |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |