Plan Review Notes
Plan Review Notes For Permit 07110403
Permit Number 07110403
Review Stop B
Sequence Number 1
Notes
Date Text
2007-11-15 15:06:34****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
  
  
 1.)EFFECTIVE OCTOBER 1, 2007, SECONDARY WATER BARRIER
 REQUIRED FS553.844(5)(A). IT IS NOT CLEAR HOW YOU
 WILL COMPLY WITH THIS REQUIREMENT FOR THE LOW SLOPED
 ROOF. PLEASE PROVIDE A WRITTEN DESCRIPTION OF EACH
 ASSEMBLY YOU ARE USING FOR THE PITCHED AND THE LOW
 SLOPED ROOF AS I WANT TO CONFIRM THAT THE PAPERWORK
 SUBMITTED IS THE PAPERWORK REQUIRED FOR YOUR JOB
 APPLICATON AND SHOWS COMPLIANCE WITH THE SECONDARY
 WATER BARRIER REQUIREMENT.
  
 2.)FOR THE FLAT DECK, SPECIFY THE ENHANCED FASTENING
 FOR CORNER AND PERIMETER ZONES.THIS IS TO BE EITHER
 WRITTEN ON THE PRODUCT APPROVAL OR SUBMITTED ON
 LETTERHEAD, TWO SETS (NOT WRITTEN ON THE RESUB SHEET).
  
  
  
  