| Plan Review Notes For Permit 07110377 |
| Permit Number |
07110377 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-12-13 16:32:42 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.ADDRESSED. | | | | | | 2.SEE SHEET 10.-75PSF REQUIRES 12" SPACING, | | | INSTALLATION SCHEDULE SPECIFIES 13.5". | | | | | | ANCHOR SPACING NOT COMPLIANT FOR DESIGN PRESSURES | | | SPECIFIED. | | | | | | 3.SHUTTER CONNECTION MOUNTING TYPE STATES TAPCON, | | | SHOULD CORRELATE WITH ANCHOR SCHEDULES, SECTIONS 1 | | | THROUGH 13, OR ALTERNATIVE SECTIONS 1 THROUGH 14. | | | | | | 4.WHAT IS THE SUBSTRATE?THE INSTALLATION SCHEDULE | | | STATES "WOOD - CBS".DOES THIS MEAN THAT IT IS CBS ON | | | THE BOTTOM, WOOD ON THE TOP? | | | | | | 5.AN EDGE DISTANCE OF LESS THAN 3 1/2" FOR CBS | | | REQUIRES USE OF A FACTOR, SEE SHEET 16. | | | | | | EDGE DISTANCE OF 1/2" AND 1 1/4" NOT ALLOWED.PLEASE | | | SEE PRODUCT APPROVAL, SHEET 10, AND REVISE INSTALLATION | | | SCHEDULE. | | | | | | | | | |
|