Plan Review Notes
Plan Review Notes For Permit 07110377
Permit Number 07110377
Review Stop B
Sequence Number 1
Notes
Date Text
2007-11-19 16:28:12****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.TWO COMPLETE COLLATED SETS REQUIRED FOR PERMIT
 ISSUANCE.
  
 2.SEE SHEET 10.-75PSF REQUIRES 12" SPACING,
 INSTALLATION SCHEDULE SPECIFIES 13.5".
  
 3.SHUTTER CONNECTION MOUNTING TYPE STATES TAPCON,
 SHOULD CORRELATE WITH ANCHOR SCHEDULES, SECTIONS 1
 THROUGH 13, OR ALTERNATIVE SECTIONS 1 THROUGH 14.
  
 4.WHAT IS THE SUBSTRATE?THE INSTALLATION SCHEDULE
 STATES "WOOD - CBS".DOES THIS MEAN THAT IT IS CBS ON
 THE BOTTOM, WOOD ON THE TOP?
  
 5.AN EDGE DISTANCE OF LESS THAN 3 1/2" FOR CBS
 REQUIRES USE OF A FACTOR, SEE SHEET 16.
  
  
  